2-6
Chapter 2: Installation and Wiring
User’s Manual Pub. 0300307-01 Rev. A
Mounting Dimensions and DIN Rail Mounting
You can install the module on DIN rails of dimension 35 mm × 7.5 mm × 1 mm
(EN 50 022-35×7.5), or on a panel.
WARNING
Hazard of intermittent grounding.
This product is grounded through the DIN rail to chassis ground. To
assure proper grounding, use zinc-plated, yellow-chromate steel DIN
rail. Using other DIN rail materials such as aluminum or plastic, that
can corrode, oxidize, or are poor conductors, may result in improper
or intermittent grounding.
Use the correct DIN rail type, and secure DIN rail to mounting surface
approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
1.
Before mounting the module on a DIN rail, use a flat-bladed screwdriver
in the DIN rail latch and pry it downwards until it is in the unlatched
position.
2.
Hook the top of the DIN rail mounting area of the module onto the DIN
rail, and then press the bottom until the module snaps onto the DIN rail.
3.
Push the DIN rail latch back into the latched position. Use DIN rail end
anchors for vibration or shock environments.
Panel Mounting
The preferred mounting method is to use two M4 (#8) screws per module. Hole
spacing tolerance is ±0.4 mm (0.016 in.). For mounting dimensions, refer to
Micro830, Micro850, and Micro870 Programmable Controllers User Manual
2080-UM002.
150 mm (5.91 in.)
Bus terminator
89 mm
(3.50 in.)
Micro850/870 Controller
2085-IF4XOF4-SC
44.5
(1 75 i )
Содержание 2085-IF4XOF4-SC
Страница 1: ......
Страница 8: ...viii Micro800TM Analog Combination I O Module User s Manual Pub 0300307 01 Rev A...
Страница 20: ...1 12 Chapter 1 Module Overview User s Manual Pub 0300307 01 Rev A...
Страница 62: ...3 34 Chapter 3 Configuring the 2085 IF4XOF4 SC Using CCW User s Manual Pub 0300307 01 Rev A...
Страница 67: ...User s Manual Pub 0300307 01 Rev A...