![Spectrum Controls 2085-IF4XOF4-SC Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/spectrum-controls/2085-if4xof4-sc/2085-if4xof4-sc_user-manual_1344803014.webp)
1-6
Chapter 1, Module Overview
User’s Manual Pub. 0300307-01 Rev. A
Output Description
Value
Voltage accuracy
(calibrated)
Error at 25 °C, Max
Error over -20 °C to 65 °C, Max
0-5 V
±5 mV
±12.5 mV
0-10 V
±20 mV
±50 mV
±10 V
±20 mV
±50 mV
Output Current Repeatability
At 25 °C
0-20 mA
Better than ±5 µA
4-20 mA
Better than ±5 µA
Output Voltage Repeatability At 25 °C
0-5 V
Better than ±0.5 mV
0-10 V
Better than ±2 mV
±10 V
Better than ±2 mV
Output Drive Capability
50 to 500 Ohm with short-circuit survival in current mode
Greater than or equal to 1 Kohm in voltage mode
Load Reactance
100 µH max in current mode
Less than 1 µF in voltage mode
Output Settling Time:
Current Output
Less than 1 ms to 63% of full scale with resistive loads
Output Settling Time:
Voltage Output
Less than 1 ms to 63% of full scale with resistive loads
Output Ripple
Less than 30 µA in current mode
Less than 15 mV in voltage mode
Fault detection
Over temperature detection is supported in both current and
voltage modes (over 150
°
C).
Open Circuit current loop detection is supported on each channel
in 4 to 20 mA range. A load resistance greater than 500 Ohm
might trigger this fault.
A short on an output pin in voltage mode will be detected, and
output current will be limited to less than 15 mA. A load less than
1 Kohm resistance also triggers this fault.
Содержание 2085-IF4XOF4-SC
Страница 1: ......
Страница 8: ...viii Micro800TM Analog Combination I O Module User s Manual Pub 0300307 01 Rev A...
Страница 20: ...1 12 Chapter 1 Module Overview User s Manual Pub 0300307 01 Rev A...
Страница 62: ...3 34 Chapter 3 Configuring the 2085 IF4XOF4 SC Using CCW User s Manual Pub 0300307 01 Rev A...
Страница 67: ...User s Manual Pub 0300307 01 Rev A...