40/40M Flame Detector
85
E
SIL-2 Features
➣
In this appendix…
page 85
E.1
40/40M Flame Detector
This appendix details the special conditions for compliance with the
requirements of EN 61508 for SIL 2.
The 40/40M Flame Detector can only be used in low or high demand mode
applications. See IEC 61508.4, Chapter 3.5.12.
E.1.1 Safety Relevant Parameters
Perform the following functional checks of the detector:
Alternative 1
: Functional check of the detector every 180 days:
HFT
: 0
PFD
: 3.3 x 10
-4
(≈ 3.
3% of SIL-2) if only alarm relay is used for
alerting
PFD
: 3.6 x 10
-4
(≈ 3.6% of SIL
-2) if 0
–
20mA interface is used as
alarm.
PFH
: 1.6 x 10
–
7
1
/
h
(≈ 16.4% of SIL
-2) for 0
–
20mA application.
SFF
: 95% fulfills the conditions of EN 61508 for SIL2
Alternative 2
: Functional check of the detector every 365 days:
HFT
: 0
PFD
: 5.1 x 10
-4
(≈ 5.1% of SIL
-2) if only alarm relay is used for
alerting
PFD
: 5.6 x 10
-4
(≈ 5.6% of SIL
-2) if 0
–
20mA interface is used
PFH
: 1.6 x 10
–
7
1
/
h
(≈ 16.4% of SIL
-2) for 0
–
20mA application
SFF
: 95% fulfills the conditions of EN 61508 for SIL2
E.1.2 Guidelines for Configuring, Installing, Operating, and
Service
The alert conditions according to SIL 2 can be implemented by an:
Alert signal via 20mA current loop
or
Alert signal via alarm relay and the fault relay
Содержание SharpEye 40/40M
Страница 2: ......
Страница 12: ......
Страница 25: ...TM 40 40M Rev 14 February 2017 Performance Considerations 25 Figure 3 Vertical Field of View for Hydrogen ...
Страница 34: ......
Страница 48: ......
Страница 56: ......
Страница 57: ...Appendix 57 Appendix ...
Страница 58: ......
Страница 66: ......
Страница 74: ......
Страница 88: ......
Страница 89: ......