Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide
60
Electrical Specifications
A.2
Electrical Specifications
Operating Voltage
: 18
–
32VDC
Power Consumption
Table 21: Electrical Specifications
Operating
Voltage
Status
All
Outputs
Without
0–20mA
Power
Consumption
(Max. 24VDC)
Normal
1.61W
1.56W
Normal when Heater On
2.28W
2.16W
Alarm
2.64W
2.28W
Alarm when Heater On
3.24W
2.88W
Maximum Current
(Max. 24VDC)
Normal
70mA
65mA
Normal when Heater On
95mA
90mA
Alarm
110mA
95mA
Alarm when Heater On
135mA
120mA
Power
Consumption
(Max. 18
–
32VDC)
Normal
1.95W
1.85W
Normal when Heater On
2.56W
2.45W
Alarm
3.04W
2.56W
Alarm when Heater On
3.68W
3.2W
Maximum Current
(Max. 18
–
32VDC)
Normal
90mA
85mA
Normal when Heater On
105mA
100mA
Alarm
130mA
115mA
Alarm when Heater On
160mA
145mA
Electrical Input Protection
The input circuit is protected against
voltage-reversed polarity, voltage transients,
surges, and spikes according to MIL-STD-
1275B
Содержание SharpEye 40/40M
Страница 2: ......
Страница 12: ......
Страница 25: ...TM 40 40M Rev 14 February 2017 Performance Considerations 25 Figure 3 Vertical Field of View for Hydrogen ...
Страница 34: ......
Страница 48: ......
Страница 56: ......
Страница 57: ...Appendix 57 Appendix ...
Страница 58: ......
Страница 66: ......
Страница 74: ......
Страница 88: ......
Страница 89: ......