Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide
50
Safety Precautions
3.2
Safety Precautions
After powering up, the detector requires almost no attention in order to
function properly, but the following should be noted:
Follow the instructions in this guide and refer to the drawings and
specifications.
Do not expose the detector to radiation of any kind unless required for
testing purposes.
Do not open the detector housing while power is connected.
Do not open the electronic compartment. This part should be kept closed
at all times and only opened in the factory. Opening the electronic
component side invalidates the warranty.
You should only access the wiring compartment to wire or remove the
detector, or to access RS-485 terminals for maintenance.
External devices such as automatic extinguishing systems must be
disconnected or disabled before carrying out any maintenance.
3.2.1 Default Functions Settings
Table 18 lists the default function configuration supplied with the detector.
Table 18: Default Function Values
Function
Value
Notes
Sensitivity
30
Alarm Delay
A
Antiflare
Alarm Latch
No
Auxiliary Relay
No
In wiring options 1, 2, and 3 the auxiliary
relay is not available. This function is not
used.
Automatic BIT
Yes
Alarm BIT
No
Auxiliary BIT
No
In wiring options 1, 2, and 3 the auxiliary
relay is not available. This function is not
used.
EOL
No
In wiring options 1, 2, and 3 the auxiliary
relay is not available. This function is not
used.
Heat Mode
Auto
Heat On
41°F/5°C The detector starts heating the window for
any temperature below this value (in
degrees Celsius).
Содержание SharpEye 40/40M
Страница 2: ......
Страница 12: ......
Страница 25: ...TM 40 40M Rev 14 February 2017 Performance Considerations 25 Figure 3 Vertical Field of View for Hydrogen ...
Страница 34: ......
Страница 48: ......
Страница 56: ......
Страница 57: ...Appendix 57 Appendix ...
Страница 58: ......
Страница 66: ......
Страница 74: ......
Страница 88: ......
Страница 89: ......