TM 40/40M, Rev (14) February 2017
Internal Detector Tests
31
Relays and heater operation
Processor watchdog
Software
Memory
Oscillator frequency
Response to Fault Indication
If a failure is found, the detector indicates by:
Fault relay:
Opens in wiring options 1, 2, and 4
Closes in wiring options 3 and 5
0
–
20mA: indicates fault (0mA or 2mA) in wiring options 1, 2, and 3
LED
–
Yellow flashes (4Hz)
Correcting the fault
The fault indications remain until the detector’s power is removed. The fault
indications return if the fault is still found when power is restored.
1.6.2 Built-In-Test (BIT)
The detector’s Built
-In-Test (BIT) also checks the following:
Electronic circuitry
Sensors
Window cleanliness
The detector can be set to perform the BIT in the following modes:
Automatically and manually
Manually only
Note:
In Manual BIT, the outputs may also be tested and Control System
“
inhibit
”
should be applied if this could initiate other systems.
How the BIT Operates
1.6.2.1
The detector's status remains unchanged if the result of a BIT is the
same as the current status (Normal or BIT Fault).
The detector
’
s status changes (from Normal to BIT Fault or vice versa) if
the BIT differs from the current status.
Note:
In
“
BIT Fault
”
status the detector can continue to detect a fire.
Содержание SharpEye 40/40M
Страница 2: ......
Страница 12: ......
Страница 25: ...TM 40 40M Rev 14 February 2017 Performance Considerations 25 Figure 3 Vertical Field of View for Hydrogen ...
Страница 34: ......
Страница 48: ......
Страница 56: ......
Страница 57: ...Appendix 57 Appendix ...
Страница 58: ......
Страница 66: ......
Страница 74: ......
Страница 88: ......
Страница 89: ......