TM 40/40M, Rev (14) February 2017
Internal Detector Tests
33
Manual BIT
1.6.2.3
The BIT is manually initiated by momentarily connecting Terminal 3 with
Terminal 2 (or a switch across these terminals in the safe area).
The results of a successful and unsuccessful Manual BIT are listed in
Table 12 and Table 13.
Table 12: Results of a Successful Manual BIT
Output
Result
Fault Relay
Wiring options 1, 2, and 4: remains Closed (Normal)
Wiring options 3 and 5: remains Open (Normal)
Alarm Relay
Activated for 3 sec (only when the function
alarm BIT
is
set to YES)
Auxiliary
Relay
For wiring options 4 and 5: is activated for 3 sec (only
when the function
auxiliary BIT
is set to
Yes
)
0
–
20mA
Output
Wiring options 1, 2, and 3:
Initiates 20mA only when the function alarm BIT is set
to Yes
Initiates 16mA when the function auxiliary BIT is set to
Yes and the function alarm
BIT
is set to
No
Power LED
Green, Flashing, 1Hz
Table 13: Results of an Unsuccessful Manual BIT
Output
Result
Fault Relay
Wiring options 1, 2, and 4: changes to Open
Wiring options 3 and 5:changes to Closed
0
–
20mA
Output
Wiring options 1, 2, and 3: Indicates BIT Fault (2mA)
Power LED
Yellow, Flashing, 4Hz
Manual BIT only selected
1.6.2.4
The BIT is initiated manually by momentarily connecting Terminal Number 3
with Terminal Number 2 (or a switch across these terminals in the safe
area).
Содержание SharpEye 40/40M
Страница 2: ......
Страница 12: ......
Страница 25: ...TM 40 40M Rev 14 February 2017 Performance Considerations 25 Figure 3 Vertical Field of View for Hydrogen ...
Страница 34: ......
Страница 48: ......
Страница 56: ......
Страница 57: ...Appendix 57 Appendix ...
Страница 58: ......
Страница 66: ......
Страница 74: ......
Страница 88: ......
Страница 89: ......