3.7.1 MINIMUM DIMENSIONS FOR FIREPLACES CRE-
ATED BY CRAFTSMEN
3.7.1.1 QUADRA INSIDE I SL
• The minimum width of fireplace measures 750 mm.
• The height of the fireplace insert measures at least 350 mm.
• The depth of the fireplace insert is defined as 400 mm.
• The distance from front edge of combustion chamber to housing frame
is defined as 50 mm.
• The cutaway in the base of the combustion chamber (support panel of
the Quadra Inside I) measures 689 x 224 mm.
• The minimum distance between housing and housing area base meas-
ures 70 mm.
• The minimum width of combustion chamber measures 750 mm.
• The minimum depth of housing area measures 360 mm.
• The minimum free cross section for the additional air aperture on
the housing area measures 200 cm².
• The combustion chamber is made of vermiculite slabs or ob calcium
silicate slabs with a material thickness of at least 40 mm. These building
materials must be approved by the German Institute of Building Tech-
nology in Berlin (DIBt), to verify their suitability for use as combustion
chamber lining.
• The thermal insulation to be used comprises mats, slabs or pipe sections
of silica-based insulation material (stone or slag and ceramic fibres) of
material class A1 as per DIN 4102, part 1 with an upper application
limit temperature of at least 700°C when measured as per DIN 52271
and a rated gross density of 80 kg/m³. When using insulating materials
of this type, ensure they are provided with an AGI-Q 132 code number
(details of thermal insulation thickness (Fig. 28) refers to mineral wool,
as defined in AGI Q 132).
• Ensure that additional air can flow into the housing area without obstruc-
tion. Free cross section for additional air is 200 cm². For this, provide
appropriate additional air apertures.
• The Quadra Inside must be bolted to the support panel using 6 appropri-
ate screws.
1
Firebox
5
Vermiculite or calcium silicate slab
t
≥
40 mm
2
Housing area
6
Mineral wool insulation
(in acc. with AGI-Q 132) t
≥
60 mm
3
Quadra Inside
7
External cladding
4
Additional air aperture
Free cross section, min. 200 cm²
min.
min.
min.
Fig. 28 Minimum distances from fire area