3.7 GENERAL NOTES ON INSTALLATION IN OPEN
FIRE AREAS / FIREPLACE INSERTS BUILT BY
CRAFTSMEN
• A bespoke, open fire area always comprises the combustion chamber,
the housing area with air inlet and the insulation or, where applicable,
front-mounted masonry.
• The combustion chamber must NOT be sealed with a firebox door.
• All inlet apertures and rear ventilation features must be left unob-
structed, and must not be blocked since otherwise a heat build-up would
take place.
Risk of fire!
• The minimum cross section at the free aperture for additional air in a
furniture unit measures:
Quadra Inside I SL – 200 cm²
Quadra Inside II SL – 400 cm²
Quadra Inside III SL – 600 cm²
• The rear ventilation features must be dimensioned appropriately.
• The Quadra Inside models must be secured to the base of the com-
bustion chamber (support panel in the Quadra Inside models) using 6
appropriate screws.
• The floor plate of the combustion chamber (with a cutaway for the
Quadra Inside) must be dimensioned appropriately.
Variants of open fireplace inserts: Quadra Inside I SL
Variants of open fireplace inserts
A
Front variant
B
Corner variant, left
C
Corner variant, right
D
Three-sided open variant
E
Transparent variant
Fig. 25