If the LAN cable must be pulled out and your hands cannot reach the lock part of
the connector, use a flathead screwdriver to press the lock part and pull out the
cable. Forcibly inserting your fingers may result in damage to the PCI Express
(PCIe) card.
■
Do not place anything on the server. Do not perform any work directly above it.
■
Be careful not to allow the ambient temperature to rise sharply in winter. Such a
sudden temperature change would cause condensation to form inside the server.
Allow for a sufficient warm-up period prior to operation.
■
Avoid installing the equipment near a copy machine, air conditioner, welding
machine, or any other devices generating electronic noise.
■
Do not install the server on the same circuit as devices, such as equipment
elevators, that can cause voltage sags when it is started.
■
Take measures to prevent static electricity from being generated at the installation
location.
■
Confirm that the supply voltage and frequency match the electrical ratings
indicated on the server.
■
Do not insert anything into any opening in the server. The server contains high-
voltage parts. If a metal object or another conductor were inserted into an
opening in the equipment, it could cause a short circuit that may result in fire,
electric shock, or equipment damage.
■
For details on maintenance of the server, contact a certified service engineer.
2.2
Before Installing the Server
Before installing the server, you must know the system configuration and obtain all
the prerequisite information for system installation. For the environmental
requirements for server installation, refer to the
SPARC Enterprise M3000 Server Site
Planning Guide
.
2.2.1
Preparing Power Supply Equipment
This section describes the electrical specifications, power cord specifications, facility
power requirements, and grounding for the M3000 server.
To prevent catastrophic failures, the facility power design must ensure that sufficient
redundant power is provided to the system. Use a dedicated power distribution
panel for all power supply lines supplying power to your server. Electrical work and
installation must comply with the applicable local, state, or national electrical codes.
Содержание Enterprise M3000
Страница 4: ......
Страница 8: ...viii SPARC Enterprise M3000 Server Installation Guide March 2012 ...
Страница 34: ...3 14 SPARC Enterprise M3000 Server Installation Guide March 2012 ...
Страница 42: ...4 8 SPARC Enterprise M3000 Server Installation Guide March 2012 ...
Страница 60: ...B 10 SPARC Enterprise M3000 Server Installation Guide March 2012 ...