6
No
Meaning
Range
Change
Factory Setting
0
Cooling setting water temperature
10 - 27°C
YES
27
1
Heating setting water temperature
10 - 27°C
YES
27
2
Turnround of defrosting under heat mode
30 - 90 min
YES
45 min
3
Defrosting start temperature
-30 - 0°C
YES
-7°C
4
Defrosting exit temperature
2 - 30°C
YES
13°C
5
Time of exit defrost under heat mode
1 - 12min
YES
5 min
6
Mode (cool/cool&heat/electric heat/heat)
0/1/2/3
YES
1
7
Mode of electronic expansion valve (0 for
‘MAN’ and 1 for ‘AUTO’)
0/1
NO
1
8
Heating Target Superheat
-15 - 15°C
NO
3°C
9
Cooling Target Superheat
-15 - 15°C
NO
3°C
A
Auto mode setting water temperature
10 -27°C
YES
27
b
Compressor protection exhaust temperature
85 - 110°C
NO
95°C
c
Low ambient temperature protection
-20 - 10°C
YES
-7°C
d
Manual control for EE valve
18 - 94
NO
70
E
Water temperature
-9 - 99°C
Measured value
F
Compressor exhaust temperature
-9 - 125°C
Measured value
G
Heating coil temperature
-9 - 99°C
Measured value
H
Return gas temperature
-9 - 99°C
Measured value
L
Ambient temperature
-9 - 99°C
Measured value
N
Cooling temperature
-9 - 99°C
Measured value
P
Actual open steps of EE valve
N*5
Measured value
on
off
Mode
SET
off
on
AUTO
12.00
MODE button
LED display
DOWN button
CLOCK button
ON/OFF button
UP button
SET button
TIMER button