background image

14

4.6  Three Phase Protection

If the phases are connected in the wrong order due to electrical mis-wiring, this protection 
system will interrupt the power supply to prevent damage to the unit. There will be an EE 4 
error code on the display.

5. Installation

5.1 Recommended Air Flow Requirements

•   The series of heat pumps must be located outside in a clean area where air flow will not   
     be restrictive. The heat pump must be located external to the spa pool cabinet to allow  
     sufficient air flow for optimum efficiency.

•   The heat pump must operate with a clean air supply so should be situated away from       
     vegetation and obstacles.

WARNING: 

The heat pump MUST be installed according to the air space requirements 

shown in Figure 1. Failure to follow these instructions may

 

VOID WARRANTY.

Содержание Power Smart SHP-100

Страница 1: ...Innovative Spa Pool Solutions INSTALLATION MAINTENANCE MANUAL SHP 60 SHP 80 SHP 100 SHP 140 SHP 170 SHP 190 ...

Страница 2: ...erheating protection on the compressor 4 4 Automatic defrost control 4 5 Anti frost protection during winter 4 5 1 First anti frost protection 4 5 2 Second anti frost protection 4 6 Three phase protection 5 Installation 5 1 Recommended air flow requirements 5 2 Location of the unit 5 3 Installation of water 5 4 Heat pump plumbing diagram 5 5 Electric connection 6 Water flow and refrigerating circu...

Страница 3: ...ldren should be supervised to ensure that they do not play with the appliance The installation commissioning and maintenance of these machines should be performed by qualified personnel having a good knowledge of standards and local regulations as well as experience with this type of equipment It is the responsibility of the installer to ensure circuit breaker protection considering the heat pump ...

Страница 4: ...act your dealer or authorized service agent for assistance Turn the mains power OFF before touching or modifying any cable connection Low voltage or improper wiring may cause damage to this appliance Read and follow all wiring instructions when connecting to power supply If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order ...

Страница 5: ...4 3 5 8 9 7 11 5 14 5 Cooling nominal intensity A 5 8 7 8 13 6 16 20 3 Air flow m3 h 1700 1700 3200 4000 4000 Noise level d B A 48 49 52 53 54 Refrigerant gas R410a R410a R410a R410a R410a Rate of average filling of gas g 620 850 1450 1650 2100 Net weight of the unit kg 51 55 77 97 100 Overall sizes L x W x H cm 99x36 x62 99x36 x62 112x48 x84 112x48 x84 112x48 x84 Possible variations of value acco...

Страница 6: ...NO 3 C 9 Cooling Target Superheat 15 15 C NO 3 C A Auto mode setting water temperature 10 27 C YES 27 b Compressor protection exhaust temperature 85 110 C NO 95 C c Low ambient temperature protection 20 10 C YES 7 C d Manual control for EE valve 18 94 NO 70 E Water temperature 9 99 C Measured value F Compressor exhaust temperature 9 125 C Measured value G Heating coil temperature 9 99 C Measured v...

Страница 7: ...Operation Parameter 1 Press hold the SET button for 5 seconds to enter the operation parameter setting interface 2 Press or to check parameter parameter from 0 P see Operation Parameter Table 3 Under parameter press SET to start setting the parameter displayed blinks Press or to set data for parameter from 0 d Press SET again to exit the current parameter settings 4 Wait for 5 seconds The LCD scre...

Страница 8: ...utes 4 13 5 5 on off Mode SET off on AUTO on off Mode SET off on AUTO on off Mode SET off on AUTO on off Mode SET off on AUTO Parameter 6 Mode 0 1 2 3 Factory setting 1 Parameter 8 Heating target superheat 15 15 C Factory setting 3 C Parameter 7 Mode of electronic expansion valve 0 for MANUAL and 1 for AUTO Factory setting 1 Parameter 9 Cooling target superheat 15 15 C Factory setting 3 C 6 1 8 3 7 1 9 3 ...

Страница 9: ...perature protection 20 10 C Factory setting 7 C Parameter d Manual control for EE valve 18 94 Factory setting 70 on off Mode SET off on AUTO ON OFF button 27 on off Mode SET off on AUTO on off Mode SET off on AUTO Parameter A Auto mode setting water temperature 10 45 C Factory setting 27 C Parameter b Compressor protection exhaust temperature for heating 85 110 C Factory setting 95 C A 27 b 95 ...

Страница 10: ...ing mode on off Mode SET off on AUTO Heating mode 27 27 3 5 Setting Temperature Press to set temperature 1 C higher press to set temperature 1 C lower 3 4 Selecting the Operation Mode Press MODE to choose mode The mode can only be changed while ON on off Mode SET off on AUTO 27 ...

Страница 11: ... no buttons are pressed within 5 seconds the LED will display the water temperature When the unit is switched OFF the current time is displayed on off Mode SET off on AUTO on off Mode SET off on AUTO on off Mode SET off on AUTO on off Mode SET off on AUTO on off Mode SET off on AUTO on off Mode SET off on AUTO Water temperature Heating copper temperature Ambient temperature Compression protection exhaust temp...

Страница 12: ...n again to set The display should return to normal Press the off button to set the time When the time displayed blinks press the off button again and then use the arrows and to change the hour setting To change the minutes press the off button again using the and arrows Once the correct time is set press the off button again to set The display should return to normal The time setting is a 0 to 24 ...

Страница 13: ...nning When the temperature of the evaporator gets too low the automatic defrost control system will be activated This system will reverse the heat pump cycle so that hot refrigerant gas is sent through the evaporator during a brief period of time to defrost it 4 5 Anti frost Protection During Winter This protection can only be activated if the heat pump is in STAND BY mode 4 5 1 First Anti frost P...

Страница 14: ...ements The series of heat pumps must be located outside in a clean area where air flow will not be restrictive The heat pump must be located external to the spa pool cabinet to allow sufficient air flow for optimum efficiency The heat pump must operate with a clean air supply so should be situated away from vegetation and obstacles WARNING The heat pump MUST be installed according to the air space...

Страница 15: ...ets or stands a level concrete base is preferred 2 If installing the heat pump in a harsh climatic area i e sub zero temperatures snow humidity it is recommended to raise the unit 50cm above the ground 3 During installation ensure sufficient free space is left around the heat pump for future maintenance 4 The unit is air cooled It must be installed outdoor in an area with sufficient clearance to p...

Страница 16: ...e o ring 2 Use PVC priming fluid on end of water pipe and union tails before gluing Once primed glue pipes into place and ensure pipes are running straight and square into heat pump IMPORTANT Ensure the pipe work running from the heat pump to the spa pool is supported DO NOT have long runs of pipe in mid air above the ground without support Ideally return the pipes to ground level as they exit the...

Страница 17: ...located on the circuit of filtration upstream of the chemical treatment unit Connect intake outlet water PVC pipes DN50 to the the inlet outlet ports as indicated grease the threads before fixing Swimming pool Filter Technical room By pass Heat pump Blowing Chemical Treatment ...

Страница 18: ... protection Protection must be of 16 A by circuit breaker or fuse it must protect the Heat pump exclusively the circuit breaker must be specified with curve D the fuse must be specified Am Differential protection 30 mA the length of cable between the connector block of the heat pump and the circuit breaker fuse should not exceed 12 m Control The heat pump is fitted with a water flow switch which i...

Страница 19: ...mpressor from these extreme conditions When this occurs the error message EE 05 is displayed The conditions causing this situation is as follows In heating mode Insufficient water flow close the by pass valve to increase the refrigerant exchange water In cooling mode Excess water flow open the by pass valve to decrease the water flow and so the exchange water refrigerant Insufficient air flow be s...

Страница 20: ...pump a Do not attempt to adjust or service without consulting your dealer or your professional pool or air conditioning contractor b Read the entire installation and user manual before attempting to use service or adjust the unit c Start the heat pump at least 24 hours after its installation in order to prevent damage to the compressor Note Switch off the power prior to maintenance or repairs 8 3 ...

Страница 21: ...quired PP 8 CONDENSER sensor out of order Sensor open or short circuited Check or replace the sensor PP 9 Low ambient temperature protection Ambient temperature is too low or protection temperature setting set too high Check and repair EE 1 High pressure protection Insufficient water flow Pressure switch out of order Too much refrigerant gas present Check the water flow Replace the pressure switch...

Страница 22: ...22 Spa Net Pty Ltd 4 103 Railway Road North Mulgrave NSW 2756 Australia Phone 61 2 4587 7766 Facsimile 61 2 4587 8766 Email service spanet com au Website www spanet com au ...

Страница 23: ...23 ...

Отзывы: