background image

 

Form 44201129 

Oct 2019 rev A

  

11 

9.0)

 

SYSTEM EXHAUST MANIFOLD 

 

1.  All exhaust manifold tube is manufactured to a standard diameter. All joint connections, on all sizes of 
 

fittings, push fit into the relative tube and should be sealed using high temperature silicone sealant. No 

 

locking bands are required. 

 

2.  Tube joints should be made as follows:- 
 

Cut tube to length required, remove all burrs and wipe off any oil or grease with a clean rag. Apply a bead 

 

(3mm) of high temperature silicone sealant around both the outer end of the fitting and the inner end of the 

 

tube. Insert the fitting into the tube up to the raised bead around the fitting. (50mm) using a slight rotary 

 

action to spread the sealant (Fig. 11). 
 

 

NOTE: The sealant remains workable for approximately 5 minutes after application. 

 

3.  Finally, secure the joint by drilling 3 equally spaced holes (Ø5.5mm) through both the tube and fittings (one 
 

hole to be at 12 o’clock to prevent possible leakage of condensate) and rivet the tube to the fittings Ø5 x 6 

 

pop rivets. 

Fig. 11 
 
 

10.0)

 

 COMMISSIONING 

 

Inspect the installation and ensure that the appliance, exhaust manifold and any combustion air ducting has 
been assembled and installed in accordance with the relevant section of these Installation, Service and 
Operating Instructions. 
 
It is essential that all new pipework installations are purged and tested for soundness with a suitable leak 
detection fluid prior to attempting to ignite any appliance.  This work should be carried out in accordance with 
National or Local regulations. 

 
 

N.B.  DO NOT TEST FOR SOUNDNESS BY USE OF NAKED FLAMES. 

 
 
 
 
 
 
 

Spiral wound manifold

push fit fittings with raised bead

3mm bead of high temp. silicone sealant

Spiral wound manifold

3No. equally spaced holes Ø5.5mm
for Ø5mm pop rivets.
(one hole to be at 12 o'clock 
to prevent condensate leakage)

50mm

50mm

Insert fitting using 

slight rotary action 
to spread sealant

Содержание ADL25-HB

Страница 1: ...ICE INSTRUCTIONS ARE INCLUDED IN THE SEPARATE MANUALS SUPPLIED WITH EACH HEATER Models LRU25 HB LRU30 35 40 45 HB LRL25 HB LRL30 35 40 45 HB ADU25 HB ADU30 35 40 45 HB ADL25 HB ADL30 35 40 45 HB Gas F...

Страница 2: ...tem Exhaust Manifold 4 5 0 Gas Supply 6 6 0 Electrical Supply 6 7 0 System Ventilation 8 7 1 Flue Size 9 8 0 Damper Assembly Attachment Linear Models 9 8 1 Damper Assembly Attachment U Tube Models 10...

Страница 3: ...e that the burner is correct for the gas type in the building 3 0 GENERAL INFORMATION This heater is a self contained infrared radiant tube heater designed for use where flammable gases or vapors are...

Страница 4: ...lity of exposure to volatile and low flash point materials exists it could result in property damage or death This heater must not be installed in a spray booth where the heater can operate during the...

Страница 5: ...rm with the plan provided 2 For suspending the manifold it is recommended that suitable protected welded chain 3mm x 65links m stainless steel flexible wire or similar and manifold tube hangers be use...

Страница 6: ...condensate trap 15mm PVC or galvanised not copper should be U shape with a minimum depth of 250mm and with the outlet connected to a drain Fan Type 1 Fig 5 4 For fan type 3 Part No 4262254 which are...

Страница 7: ...to national or Local Regulations to connect the appliance to the gas supply Minimum size to be 12 7mm bore 3 LPG G30 G31 at 29 37mbar nominal supply pressure appliance cat 3 Maximum supply pressure Pm...

Страница 8: ...atively connection may be made via a fused 3 pin plug and un switched shuttered socket both complying with the requirements of National or Local Regulations Neither thermostat nor switch are supplied...

Страница 9: ...elow the level of the heater s Up to and including 60kW 4 5cm2 kW Over 60kW 270cm2 2 25cm2 kW in excess of 60kW total rated heat input Where the air supply openings can be closed it shall only be poss...

Страница 10: ...n the Control Box Air Inlet and any rigid ducting and be secured to the Air Inlet with hose clips The maximum length of ducting should be 15m with a maximum of two 900 bends Where outside combustion a...

Страница 11: ...Coupling up to the stop and is positioned with the adjustable slide flange at its lower edge Tighten the nuts of the Torctite Coupling to secure the Damper Assembly to the Radiant Tube taking care to...

Страница 12: ...holes 5 5mm through both the tube and fittings one hole to be at 12 o clock to prevent possible leakage of condensate and rivet the tube to the fittings 5 x 6 pop rivets Fig 11 10 0 COMMISSIONING Insp...

Страница 13: ...hing on the electricity supply to the system control and setting the time switch and thermostat to demand heat Carry out the procedures at 5 and 6 on each of the appliances in the system 5 Connect a s...

Страница 14: ...nt servicing may be desirable IMPORTANT A Do not rest anything especially ladders against the appliance B Gas and Electricity supplies must be isolated before commencing servicing work or replacement...

Страница 15: ...fan F Type 3 Fan G Remove the cover from the Exhaust Fan terminal housing and remove the electrical leads H Disconnect the flue from the fan outlet I Slacking the Hose Clips securing the Fan Connecto...

Страница 16: ...occurs switch off the electricity supply to the zone or system fan wait for 10 seconds before switching on the electricity supply to the zone or system fan to repeat the ignition sequence It is not po...

Страница 17: ...Form 44201129 Oct 2019 rev A NOTES...

Отзывы: