Combustion Air Adjustment (System Cold) 

 
 

It is necessary to adjust the amount of combustion air to each burner in the system by carring out the 

 

following procedures: 
 

1.

 

Switch off the electricity supply to each appliance in the system. 

 

2.

 

Turn off the gas supply to each appliance in the system, at their gas isolation valves. 

 

3.

 

Set the adjustable gate of each appliance damper (after unscrewing the clamp screw) such that the stop 
(rivet) is positioned against the damper housing ie. position of maximum resistance to air flow. Secure the 
adjustable gate in position with the clamp screw. See Fig. 12 below. 

 

Fig 12 

 

 

 
 

4.

 

Activate the exhaust fan by switching on the electricity supply to the system control and setting the time 
switch and thermostat to demand heat. Carry out the procedures at 5 and 6 on each of the appliances in the 
system. 

 

5.

 

Connect a suitable manometer (0.01 mbar resolution) to the test nipple protruding from the rear panel of the 
control box (adjacent to the air inlet adaptor) as outlined in separate installation and operation instructions 
manual supplied with the heater. 

 

6.

 

Reposition the adjustable gate of the appliance damper (after unscrewing the clamp screw) to attain a 
negative pressure reading on the manometer of 1.5mbar ± 0.05mbar. Secure the adjustable gate in position 
with the clamp screw 

 

7.

 

Finally, check all the test points again to verify that the negative pressure at each of the burners in the system 
is 1.5mbar ± 0.05mbar. 

 

 

Carry out the procedures of B below on each appliance in the system. 

 

 
 
 

Содержание ADL25-HB

Страница 1: ...ICE INSTRUCTIONS ARE INCLUDED IN THE SEPARATE MANUALS SUPPLIED WITH EACH HEATER Models LRU25 HB LRU30 35 40 45 HB LRL25 HB LRL30 35 40 45 HB ADU25 HB ADU30 35 40 45 HB ADL25 HB ADL30 35 40 45 HB Gas F...

Страница 2: ...tem Exhaust Manifold 4 5 0 Gas Supply 6 6 0 Electrical Supply 6 7 0 System Ventilation 8 7 1 Flue Size 9 8 0 Damper Assembly Attachment Linear Models 9 8 1 Damper Assembly Attachment U Tube Models 10...

Страница 3: ...e that the burner is correct for the gas type in the building 3 0 GENERAL INFORMATION This heater is a self contained infrared radiant tube heater designed for use where flammable gases or vapors are...

Страница 4: ...lity of exposure to volatile and low flash point materials exists it could result in property damage or death This heater must not be installed in a spray booth where the heater can operate during the...

Страница 5: ...rm with the plan provided 2 For suspending the manifold it is recommended that suitable protected welded chain 3mm x 65links m stainless steel flexible wire or similar and manifold tube hangers be use...

Страница 6: ...condensate trap 15mm PVC or galvanised not copper should be U shape with a minimum depth of 250mm and with the outlet connected to a drain Fan Type 1 Fig 5 4 For fan type 3 Part No 4262254 which are...

Страница 7: ...to national or Local Regulations to connect the appliance to the gas supply Minimum size to be 12 7mm bore 3 LPG G30 G31 at 29 37mbar nominal supply pressure appliance cat 3 Maximum supply pressure Pm...

Страница 8: ...atively connection may be made via a fused 3 pin plug and un switched shuttered socket both complying with the requirements of National or Local Regulations Neither thermostat nor switch are supplied...

Страница 9: ...elow the level of the heater s Up to and including 60kW 4 5cm2 kW Over 60kW 270cm2 2 25cm2 kW in excess of 60kW total rated heat input Where the air supply openings can be closed it shall only be poss...

Страница 10: ...n the Control Box Air Inlet and any rigid ducting and be secured to the Air Inlet with hose clips The maximum length of ducting should be 15m with a maximum of two 900 bends Where outside combustion a...

Страница 11: ...Coupling up to the stop and is positioned with the adjustable slide flange at its lower edge Tighten the nuts of the Torctite Coupling to secure the Damper Assembly to the Radiant Tube taking care to...

Страница 12: ...holes 5 5mm through both the tube and fittings one hole to be at 12 o clock to prevent possible leakage of condensate and rivet the tube to the fittings 5 x 6 pop rivets Fig 11 10 0 COMMISSIONING Insp...

Страница 13: ...hing on the electricity supply to the system control and setting the time switch and thermostat to demand heat Carry out the procedures at 5 and 6 on each of the appliances in the system 5 Connect a s...

Страница 14: ...nt servicing may be desirable IMPORTANT A Do not rest anything especially ladders against the appliance B Gas and Electricity supplies must be isolated before commencing servicing work or replacement...

Страница 15: ...fan F Type 3 Fan G Remove the cover from the Exhaust Fan terminal housing and remove the electrical leads H Disconnect the flue from the fan outlet I Slacking the Hose Clips securing the Fan Connecto...

Страница 16: ...occurs switch off the electricity supply to the zone or system fan wait for 10 seconds before switching on the electricity supply to the zone or system fan to repeat the ignition sequence It is not po...

Страница 17: ...Form 44201129 Oct 2019 rev A NOTES...

Отзывы: