8. Electrical Information
8.1 Fusing Requirements
Suggested dedicated circuit breaker sizing. Always refer to local code
regarding necessary circuit breaker requirements.
Nominal Supply Power
Full Load Amps
Required Breaker
115/1/60
27
30
208/1/60
14.3
20
230/1/60
13.5
20
208/3/60
8.4
15
230/3/60
8
15
460/3/60
4
15
190/3/50
9.4
15
380/3/50
4.7
15
Ensure the motor overload relay is set
for the correct full load amps for the
given primary voltage.
Motor Horsepower 3.2
Control Voltage 115/1/60
Primary Voltage Varies