BLASTOFF™ - LEAK DETECTION SYSTEM:
“There is an alarm sounding in the FPS-650 and
FPS-1250 and the control panel has ‘
b ōFF
’
illuminated on the side panel of the unit.”
If you hear the alarm and the “
b ōFF
” is displayed on
your unit, it
means that it is equipped with
“The BlastOff™ - Leak Detection”
feature. If the
buzzer is on, there may be a leak in one of the sprinkler lines, AMD, or fittings
may not be properly seated, causing leaks. Note: Turn off this unit’s on/off
power switch and check for leaks. If none are found, leave the unit turned off
and contact your Service Technician. Once the leak has been fixed, turn the
N
2
Blast™ on/off rocker switch back “On” to resume normal operation. By
turning the system power off, then back on, this will reset the BlastOff™
automatically.