10
Installation
3
3
3.2 Electrical connection
(continued)
Terminal connection diagram, program 2
Fig. 3.2.3 “Solar + Thermostat”
Low voltage
max. 12VAC/DC connec-
tion in the left-hand terminal compart-
ment!
Terminal: Connection
for:
S1 (2x)
Sensor 1 collector
S2 (2x)
Sensor 2 storage tank below
S3 (2x)
Sensor 3 storage tank above
The polarity of the sensors is freely
Caution
Relay R1: Only for speed control
of standard pumps, minimum
load 20VA
selectable.
Mains voltages
115VAC 50-60Hz
Connection in the right-hand terminal
compartment!
Terminal: Connection
for:
L
Mains phase conductor L
N
Mains neutral conductor N
R1
Pump L (speed)
N
Pump N
R2
Thermostat function L
N
Thermostat function N
The PE protective conductor must be
connected to the PE metal terminal block!
Sensor side
max. 12V
Danger
Caution
Mains side
115VAC
Fig. 3.2.2 “Solar with storage tank”
Terminal connection diagram, program 1
Low voltage
max. 12VAC/DC connec-
tion in the left-hand terminal compart-
ment!
Sensor side
max. 12V
Danger
Caution
Mains side
115VAC
Caution
Options for sensor 3:
display, Tmax function, heat
metering (see 12.7)
Terminal: Connection
for:
S1 (2x) Sensor 1 collector
S2 (2x) Sensor 2 storage tank
S3 (2x) Sensor 3 (optional)
The polarity of the sensors is freely
selectable.
Mains voltages
115VAC 50-60Hz
Connection in the right-hand terminal
compartment!
Terminal: Connection
for:
L
Mains phase conductor L
N
Mains neutral conductor N
R1
Pump L (speed)
N
Pump N
R2
Pump L (no speed)
N
Pump N
The PE protective conductor must be
connected to the PE metal terminal block!
Relay R1: For speed control of standard
pumps, minimum load 20VA