31. March 2017
Manual
animeo KNX Master Control W2/W8
2011-2017, SOMFY ACTIVITES SA ALL RIGHTS RESERVED 2017/03/31
75/109
4.7.3.3. Block heat
This function is normally to keep the heat out of the building by using the sun protection. This function is
normally used beyond working hours.
If inside or outside temperature plus sun rays exceed the set value, then the end products move into a
predefined position. The local control can be blocked.
This function is only carried out if no other function with a higher priority is active. The corresponding
KNX objects are KNX.MC.Zone_Energy_Saving_Bit_OUT[n],
KNX.MC.Zone_Position_UP_DOWN_1Byte_OUT[n] and KNX.MC.Zone_Slat_Position_1Byte_OUT[n],
whereby “n” stands for the respective selected zone 1-16.
Parameter:
1. Select Block Heat.
2. Enable/disable function.
3. Response time
time span, during the temperature (6) and sun rays (7) must exceed before the
function is activated.
4. Delay time
time span, during the temperature (6) and sun rays (7) must fall below before the
function is deactivated.
5. Inside or Outside
select which ambient temperature will be used for the calculation.
6. Temperature
the necessary measured temperature which must be exceeded or be below to acti-
vate or deactivate the function.
7. The sun
the necessary measured sun intensity which must be exceeded or be below to activate
or deactivate the function.
8. Position, to which is moved to with activating the function (2).
9. Angle, to which is moved to with activating the function (2).