31. March 2017
Manual
animeo KNX Master Control W2/W8
2011-2017, SOMFY ACTIVITES SA ALL RIGHTS RESERVED 2017/03/31
63/109
4.7.1.9. Zone timer
This function enables the end products of a zone, within a defined period, to move to a certain position.
When this is completed, the end products go to the upper end position (position 0 % and angle 0°).
This function is only carried out if no other function with a higher priority is active.
The corresponding KNX objects are KNX.MC.Zone_Position_UP_DOWN_1Byte_OUT [n] and
KNX.MC.Zone_Slat_Position_1Byte_OUT [n] whereby n stands for the respective selected zone 1-16.
Parameter:
1. Select zone timer.
2. Enable/disable function.
3. Open zone timer for this zone which then opens the following window.
Parameter:
1. Time interval (green) in a time line
a. Add new time interval:
With pressed mouse button, click on desired day and suitable position
bar (1). Drag the time interval (2) to the right or left. Release the mouse button. The set time is
displayed on the right beside the bar.
b. Change time interval:
With pressed mouse button on one of the bar ends of the time interval to
be changed (2), click and drag this in the desired direction. Release the mouse button. The set
time is displayed on the right beside the bar.