31. March 2017
Manual
animeo KNX Master Control W2/W8
2011-2017, SOMFY ACTIVITES SA ALL RIGHTS RESERVED 2017/03/31
59/109
Parameter:
1. Updating time: gives the time between two position calculations.
2. Façade orientation: Orientation of the zone, set under setting - zones (chapter 4.4.2.8).
3. Slats – distance/width: Ratio between slats distance and slats width. This parameter is used for the
calculation of the sun tracking to ensure an optimum ratio of brightness and glare protection.
4. Minimum step: States the minimum percent value which must be calculated from the position before
a move command can be carried out.
5. Degree of longitude: Provides the geographical length of the building. Setting is done under settings
– position (chapter4.4.2.7).
6. Degree of latitude: Provides the geographical width of the building. Setting is done under settings –
position (chapter 4.4.2.7).
7. Azimuth: Horizontal angle of the current sun tacking.
8. Elevation: Height angle of the current sun tracking.
9. Time zone: States the time zone of the building. Setting is done under settings – zones (chapter
4.4.2.5).
10. “Apply” for taking on the settings.
11. “Cancel” for quitting without settings.
12. Graphic display of the end product. Setting is done under settings - zones (chapter 4.4.2.8).