4.7.1.2. Wind direction
With the wind direction function it can be ensured that the end products do not become damaged by
wind from a particular direction. The wind direction only works in connection with the first wind sensor
(Wind1).
If the wind set value is exceeded and lies in the protected area, the corresponding KNX object
(KNX.MC.Zone_Security_High_Prio_Bit_OUT) will transmit 1.
2
3
1
6
4
5
Parameter:
1. Select wind function.
2. Enable/disable function.
3. Set wind speed value
necessary measured wind speed to trigger the function.
4. Monitored direction
wind direction for the protective angle by rotating the button to the left or on
the right, so that the alignment of the selected façade lies in the middle of the lighted diode ring.
5. Monitored zone
the size of the protective angle is varied by pulling the bar to the right or left.
Generally, the protective angle is 180 ° and the direction will be measured according to the orienta-
tion of the façade center.
6. The function wind direction uses the response times and delay times of the wind function.
4.7.1.2.1.
Use Of KNX Object Low Prio
With “Use KNX Object Low Prio” will be two KNX objects (KNX.MC.Zone_Security_Low_Prio_Bit_OUT)
and (KNX.MC.Zone_Security_High_Prio_Bit_OUT) active.