31. March 2017
Manual
animeo KNX Master Control W2/W8
2011-2017, SOMFY ACTIVITES SA ALL RIGHTS RESERVED 2017/03/31
56/109
4.7.1.5.1.
Position OFF Settings
Parameter:
1. “Keep Current Position“:
if sun intensity falls below the adjusted sun off threshold, then the end
product will stay in the current position.
2. “Open Slats“:
if sun intensity falls below the adjusted sun off threshold, then the end product will
stay in the current position and only the slats will move into the horizontal position. Not in all end
products available.
3. “Position / Angle“:
if sun intensity falls below the adjusted sun off threshold, then the end product
will move into the set position (a) and angle (b). Angle (b) not in all end products available.
a. Position: the position which is moved to by not reaching the set points.
b. Angle: the angle which is moved to by not reaching the set points. Not in all end products avail-
able.
4. “Apply” for taking on the setting.
5. “Cancel” for quitting without settings.
4.7.1.6. Sun tracking
The function is not available for windows, folding arm awnings and screens.
This function aligns the position of the end products automatically to the sun‘s angle. Select the option
“Sun tracking” (1) and click on the button on the right “Settings” (2).
This function is only carried out if no other function with a higher priority is active. The corresponding KNX
objects are KNX.MC.Zone_Position_UP_DOWN_1Byte_OUT , KNX.MC.Zone_Slat_Position_1Byte_OUT and
KNX.MC.Zone_Sun-Function_Bit_OUT.
Parameter:
1. Select sun tracking.
2. Settings; an extra window is opened for setting sun tracking (see picture below).