![SolutionAir GRW Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/solutionair/grw/grw_manual-installation_1317081019.webp)
GRW
Maintenance
17
SolutionAirGroup.com
|
GRW - Manual
Maintenance Checklist
General Maintenance
Quarterly
Annually
Inspect inside of unit for water leaks, foreign material etc.
X
Clean or replace filters with equivalent to those supplied by manufacturer.
X
Check cooling device drain pans and traps for cleanliness and blockage – ensure chemical cleaner is
compatible with aluminum.
X
Check all dampers and damper actuators, adjust and tighten as required.
X
Check cooling coils for cleanliness and clean as necessary.
X
Inspect for worn compressor contactors annually and replace every 5 years
X
Remove and lubricate stainless steel bolts
X
Blower/Fan Maintenance
Check all bearings and lubricate as necessary.
X
Inspect fan wheel and housing. Clean as necessary.
X
Electrical Maintenance
Check for loose wire connections in control panel.
X
Check motor amp draw against name plate.
X
Inspect all contactors to ensure they are clean and making good contact.
X
Check all safeties.
X