GRW
Installation
11
SolutionAirGroup.com
|
GRW - Manual
Split Roof-Seam Sealing
Procedure
Sealing Roof Seams at GRW Splits:
1. Seal ends of roof-seam at GRW
unit splits with Emseal end-dams.
a) Cut Emseal strips roughly 1”
longer than the distance from
the existing Emseal to the
blower/coil roof flange. Do not
remove backing.
b) Cut black Emseal sponge
back by roughly 1.25”, without
cutting the clear backing
(Figure 12).
c) Dog-ear the top of the Emseal
strip (partially remove the clear
plastic backing), enough to be
able to firmly grasp from the
edge.
d) Place Emseal strip firmly
against existing Emseal
(spanning the split between
the sections) and ¼” from
edge of coil/blower roof
(Figure 13).
e) Once satisfied with the
placement, carefully remove
clear backing. Let Emseal strip
expand into place (may take
5-60 minutes, depending on
outdoor temperature and
humidity).
f) Repeat the above steps for
each roof-seam end (four total
for each unit).
2. Firmly apply sealing tape (such as
3” wide 3M 8777) over the
interior
roof-seams between the coil and
blower/filter sections, to prevent
any sealant drips from entering the
unit.
3. Firmly apply removable tape
(painters tape) along the blower/
filter roof flange (Figure 14), to help
prevent any sealant drips.
FIGURE 12: DOG EARRING INSTRUCTIONS
FIGURE 13: EMSEAL BACKING PLACEMENT
DOG-EARED BACKING
TOP VIEW
SIDE VIEW
TOP VIEW
BOTTOM VIEW
SIDE VIEW
TOP VIEW
BACKING
EMSEAL
EMSEAL
END-DAM
COIL
SECTION
COIL ROOF
FILTER/
BLOWER ROOF
FILTER/
BLOWER ROOF
~1.25
~0.25”
FIGURE 14: REMOVABLE TAPE PLACEMENT
SIDE VIEW
TOP VIEW
PAINTER’S TAPE
COIL
SECTION
COIL ROOF
FILTER/
BLOWER ROOF
FILTER/
BLOWER ROOF