22 UM0012_ASW 5-10k Series_EN_V03_0522
Object
Description
Value
A
External diameter
14 to 20mm
B
Conductor cross-section
6 to 16 mm²
C
Stripping length of the insulated conductors
approx. 16 mm
D
Stripping length of the outer sheath of cable
approx. 46 mm
Larger cross-sections should be used for longer cables.
Cable design
The conductor cross-section should be dimensioned to avoid power loss in
cables exceeding 1% of rated output power.
The higher grid impedance of the AC cable makes it easier to disconnect from
the grid due to excessive voltage at the feed-in point.
The maximum cable lengths depend on the conductor cross-section as
follows:
Conducto
r cross-
section
Maximum cable length
ASW5000-S
ASW5000-S-A
ASW6000-S
ASW6000-S-A
ASW8000-S
ASW8000-S-A
ASW10000-S
ASW10000-S-A
8 mm²
15m
15m
11 m
9m
10 mm²
18m
18m
14 m
11m
The required conductor cross-section depends on the inverter rating, ambient
temperature, routing method, cable type, cable losses, applicable installation
requirements of the country of installation, etc.
Residual current protection
The product is equipped with an integrated universal current-sensitive residual
current monitoring unit inside. The inverter will disconnect immediately from
the mains power as soon as fault current with a value exceeding the limit.