T
HERMO
C
UBE
200/300/400
T
HERMOELECTRIC
C
HILLER
M
ANUAL
52-11300-1
S
OLID
S
TATE
C
OOLING
S
YSTEMS
,
167
M
YERS
C
ORNERS
R
OAD
,
W
APPINGERS
F
ALLS
,
NY
12590
24
T
ELEPHONE
:
(845)
296-1300
F
AX
:
(845)
296-1303
WEB
:
WWW
.
SSCOOLING
.
COM
V
ERSION
M28
-EF: External Filter Option
This option adds an external 5 micron filter to the ThermoCube
coolant outlet for systems sensitive to particulate matter in the
coolant. Note that this option also dampens coolant flow pulses,
producing a smoother coolant flow.
-FL: Fluorinert or Galden
This option is selected to configure the ThermoCube for
perfluorinated or hydro fluorinated ether processs fluids such as
Fluorinert or Galden. CAUTION: Make sure this option is included
in your ThermoCube configuration if you plan to use these process
fluids.
-HT: High Temperature Operation Option
The ThermoCube normally has a 55 °C thermostat on its liquid cold
plate that shuts off heating to protect against hot coolant damaging
the operator’s equipment. The –HT option replaces this thermostat
with a 70 °C thermostat and adds insulation to allow operation up
coolant temperatures of 65 °C. Note: The Maximum specified
temperature for standard Centrifugal pumps (-1C and -1CL) is 60 °C.
-LT: Low Temperature Operation Option
The ThermoCube normally has a 5°C thermostat on its liquid cold
plate that shuts off cooling to prevent freeze damage when using
water as a coolant. The –LT option removes this thermostat and
adds insulation to allow operation below the freezing point of water
(0°C). Select this option if you plan to regularly run at setpoints
below 8-10°C. When selecting this option, the operator must ensure
coolants are selected that will not freeze within 5°C of set point.
Repairs to thermoelectric heat exchangers damaged by freezing
water in Thermocubes with this option selected will not be covered
by warranty.
-PT: Preset Control Temperature
With this option the ThermoCube is shipped from the factory with a
preset control temperature specified by the customer, and manual
entry is disabled. The ThermoCube will always control to the preset
temperature and the user no longer has the ability to modify the
settings of the unit.
CAUTION