Parallel operation elements
Solé, S.A. C-243 b, km 2 · 08760 Martorell (Barcelona) ·Tel. +34 93 775 14 00 · www.solediesel.com · [email protected]
55
Marine Diesel gensets. O
perator’s Manual.
2.
Check the current on the wire of PIN A to actuator at 1500 RPM. Increase the load and
measure the current, it should increase. If don’t increases the ECU don’t operates correctly.
3.
Check the resistance between PIN C and PIN D.
Terminals
Value
Nominal current
4,0 A (12 V DC)
2,0 A (24 V DC)
Max. Continuous current
5,8 A (12 V DC)
3,1 A (12 V DC)
Nominal coil resistance
7,2 Ω
2,0 Ω
Terminals
Value
C & D
30 Ω to 1200 Ω