7 • Technical Data
________________________________________________________________________________________________
WARNINGS!
The heatsink over temperature protection is designed to operate under normal
conditions and will operate in case abnormal conditions occur:
•
Incorrect starter selection
•
Too frequent starting at maximum conditions
•
Repeated starting under fault conditions
•
Extended low overload
•
Insufficient ventilation
•
Other abnormal conditions
Note
-
In case of frequent starting the internal thyristors may overheat before the
heatsink reaches its over-temperature protection of 85ºC, thus causing
component malfunction.
3.7
Starter selection tables for various voltage ratings.
1
The starter selection table below concern standard, 1500r.p.m. 50Hz,
three-phase motors.
2
These values are given for guidance and may vary according to motor
manufacturer and depending on the number of poles.
3
It is the user’s responsibility to make sure that motor’s FLA will never
exceed Starter’s FLC.
Starter type
Starter FLC
[A]
Motor kW
@230V
[kW]
Motor kW
@400V
[kW]
Motor kW
@480V
[kW]
Motor kW
@600V
[kW]
Solstart Plus 31
31
8
15
18.5
25
Solstart Plus 44
44
12.5
22
25
30
Solstart Plus 58
58
15
25
37
45
Solstart Plus 72
72
20
37
45
59
Solstart Plus 85
85
25
45
55
59
Solstart Plus 105
105
30
55
59
80
Solstart Plus 145
145
40
75
90
110
Solstart Plus 170
170
51
90
110
140