17 • STARTING PROCEDURE
________________________________________________________________________________________________
8.
STARTING PROCEDURE
1
When mains voltage is connected to the Solstart Plus, even if control
voltage is disconnected, full voltage may appear on the starter load
terminals. Therefore, for isolation purposes, it is necessary to connect an
isolating device before (upstream) the starter.
2
Power factor correction capacitors must not be installed on starters load
side. When required, install capacitors on starter’s line side.
3
Before starting the motor verify its rotation direction. If needed,
disconnect the rotor from the mechanical load and verify the right rotation
direction.
4
Prior to Start up procedure make sure that line voltage and control
voltage match the ones shown on the starter’s name plate.
5
Do not interchange line and load connections
6
Do not connect the Solstart Plus “Inside delta”.