background image

5 • Technical Data 

________________________________________________________________________________________________ 

 

3.4

 

Mains and control description 

3.4.1

 

Mains Voltage (line to line)(Terminals/bars L1, L2, L3) 

Four mains voltage levels are available: 208V, 400V, 480V, 600V.  

Note: 

208V applies for 208V-10% up to 

220V

+15% 

400V applies for 400V-10% up to 400V+15% 
480V applies for 480V-10% up to 480V+15% 
600V applies for 600V-10% up to 660V+15% 

 

 

3.4.2

 

Control Voltage (Terminals 1, 2) 

The Solstart Plus incorporates a universal power supply unit for DC and AC control voltage. 
110-230V, 50/60Hz or 110-230VDC (+10%/ -15%) is required to power the electronic circuitry and the bypass.  
This voltage can be from a grounded or ungrounded mains system.  
 

3.4.3

 

Discrete input voltage (Terminals 3, 4) 

Apply discrete input voltage to terminals 3 and 4 to soft start the motor. 
To stop the motor disconnect the control voltage from terminals 3 and 4. If Deceleration time is set to a value 
other then 0 seconds the motor will soft stop. 
Discrete input voltage should be in the same range as control voltage: 110-230V, 50/60Hz or 110-230VDC 
(+10%/ -15%). 
This voltage can be from a grounded or ungrounded mains system. 
 

3.4.4

 

End Of Acceleration (terminals 5, 6)- Solstart Plus 58A and up. 

This contact exists in Solstart Plus 58A and up. 
Voltage free, N.O., 8A / 250VAC, 1800VA max.  
The contact closes after the time adjusted on the "Ramp-Up" potentiometer. The contact returns to its original 
position on stop signal, on fault condition, upon voltage outage and at the beginning of Soft Stop. 
This contact can be used for: 

 

Activating a valve after a compressor has reached full speed. 

 

Activating a valve after a pump has reached full speed. 

 

Loading a conveyor after the motor has reached full speed. 

 

3.4.5

 

Fault Contact (terminals 7, 8) 

Voltage free, N.O , 8A, 250VAC, 1800VA max. Solstart Plus 58A and up. 
Voltage free, N.O , 5A, 250VAC, 1250VA max. Solstart Plus up to 44A. 
The contact changes its position upon fault and returns to its original position after fault has been removed 
and starter was reset. When disconnection of control supply the contacts will be opened. 
 

3.5

 

Built-in Bypass 

The Solstart Plus incorporates two internal bypass relays allowing current flow through the thyristors only 
during starting process. At the end of the starting process, the built-in relays bypass the thyristors and carry 
the current to the motor.  
Upon stop signal, or in case of fault, both bypass relays will open and stop the motor.  
When Ramp-Down potentiometer is set to allow soft-Stop process, upon stop command, the bypass relays will 
open immediately and the current will flow through the thyristors. The voltage will then be reduced slowly and 
smoothly to zero. 

Содержание Solstart Plus 105

Страница 1: ...So ol ls st ta ar rt t P Pl lu us s A An na al lo og g S So of ft t S St ta ar rt te er r 3 31 1 1 17 70 0A A 2 20 08 8 6 60 00 0V V I In ns st tr ru uc ct ti io on n M Ma an nu ua al l Ver 29 04 200...

Страница 2: ...erload 6 3 6 2 Phase Loss 6 3 6 3 Under voltage 6 3 6 4 Heatsink over temperature protection 6 3 6 5 Fault Logic and Reset Circuits 6 3 7 Starter selection tables for various voltage ratings 7 3 7 1 O...

Страница 3: ...2 Attention 1 This product was designed for compliance with IEC 947 4 2 for class A equipment 2 Use of the product in domestic environments may cause radio interference in which case the user may be...

Страница 4: ...3 Starter Selection Select the starter according to motor s Full Load Ampere FLA as indicated on its nameplate even if the motor will not be fully loaded The Solstart Plus is designed to operate under...

Страница 5: ...s contact exists in Solstart Plus 58A and up Voltage free N O 8A 250VAC 1800VA max The contact closes after the time adjusted on the Ramp Up potentiometer The contact returns to its original position...

Страница 6: ...es operational when the starter is energized it protects the motor from under voltage It will trip the starter when under voltage condition occurs for more than 1 sec When this protection activates Fa...

Страница 7: ...ection of 85 C thus causing component malfunction 3 7 Starter selection tables for various voltage ratings 1 The starter selection table below concern standard 1500r p m 50Hz three phase motors 2 Thes...

Страница 8: ...to 600V 10 Control Voltage Specify Description 2 110 230 VAC50 60Hz DC 15 10 Note Solstart Plus incorporates a universal power supply unit for DC and AC control voltage Options Specify Description 0...

Страница 9: ...tage can be from a different voltage system then the control voltage or of the same system 4 End Of Acceleration contact EOA exist in models Solstart Plus 58 and up 5 Fault contact closes in fault con...

Страница 10: ...to fuse manufacturer catalogs to confirm correct values 4 2 2 Transient Protection Line transient voltages can cause a malfunction of the starter and damage to the thyristors All Solstart Plus starte...

Страница 11: ...Dimensions ________________________________________________________________________________________________ 5 DIMENSIONS Solstart Plus 31 44 Note Mains voltage terminals 16mm2 Solstart Plus 58 72 85 1...

Страница 12: ...l voltages are as indicated on the starter s side label Make sure Starter s FLC Motor FLA Make sure Mains voltage is right Make sure Control voltage is right Solstart Plus label example 6 2 Mounting T...

Страница 13: ...nd soft stop heating is approximately two times the actual starting current In watts Example For a 100A motor heat dissipation is less than 30 watts while running and during starting for example at 35...

Страница 14: ...Reset Button 7 1 Potentiometers settings Potentiometer Range Description Motor FLC 50 100 The adjustment allows easy setting of the Solstart Plus current level automatically adjusting current based f...

Страница 15: ...arting Range is 100 400 of FLC as set on motor s FLC adjustment Too high of a setting will allow higher currents to be drawn from mains resulting in faster acceleration Too low of a setting may preven...

Страница 16: ...button Green On Will lit when Control Supply voltage is connected to the starter Yellow Ramp Up Down Will lit during soft start and soft stop process indicating that motor supply voltage is ramping up...

Страница 17: ...lating device before upstream the starter 2 Power factor correction capacitors must not be installed on starters load side When required install capacitors on starter s line side 3 Before starting the...

Страница 18: ...Connect mains voltage to starter line terminals 5 Apply Start command Motor starts to turn shortly after Start Initial inrush current or mechanical shock is too high Increase Initial Voltage and start...

Страница 19: ...neously increase to peak current value which can be the Current Limit setting or less before smoothly decreasing to the operating current The motor will accelerate to full speed quickly and smoothly H...

Страница 20: ...ault LED lights and Fault Relay operates Fault Massage Cause and trouble shooting Overload LED lights Trips the starter when current exceed the overload level and thermal register has filled up Check...

Страница 21: ...umber And Build Options Example 170 400 2 8 S Solstart Plus _ _ _ _ _ _ _ __ ___ _ Serial Number Purchasing Date Sale Installation Date Failure Date Draw one line diagram Draw control diagram Define t...

Страница 22: ...rips when voltage is not within allowed limits Heatsink Over temperature Trips when the heatsink temperature exceeds 85 C Reset buttons To reset the starter after the fault has been removed Indication...

Страница 23: ...Acceleration Contact Exists in models Solstart Plus 58A and up N O 8A 250VAC 1800VA max Fault contact N O 5A 250VAC 1250VA max Solstart Plus up to 44A N O 8A 250VAC 1800VA max Solstart Plus 58A and u...

Отзывы: