Solstart Plus 145, 170
6.
INSTALLATION
Do not interchange line and load connections
WARNING!
Do not connect the Solstart Plus “Inside Delta”
6.1
Prior to Installation
Check that Motor’s Full Load Ampere (FLA) is lower than, or equal, to the starter’s Full Load Current (FLC)
and that Mains and Control voltages are as indicated on the starter’s side label.
Make sure Starter’s FLC
≥
Motor FLA!
Make sure Mains voltage is right!
Make sure Control voltage is right!
Solstart Plus label - example
6.2
Mounting
The starter must be mounted vertically. Allow sufficient space (at least 100mm) above and below the starter
for suitable airflow.
It is recommended to mount the starter directly on the rear metal plate for better heat dissipation.
Do not mount the starter near heat sources.
Surrounding air temperature in the cabinet should not exceed 40ºC
Protect the starter from dust and corrosive atmospheres.