Introduction

Introduction

13

3.2 Work Modes

X3-Retro Fit Series inverter provides multiple work modes based on different 
requirements.

3.3 Dimension

457 mm

6

5

4 m

m

228 mm

12

·

In the absence of the external generator, or 

the power is not enough, battery will 
discharge for local loads first, and grid will 
supply power when power from the battery 
is not enough or battery reaches the minium 
capacity.

Work modes:  

Feed in Priority

Priority:load>grid>battery

This mode applies to the area that has high 
feed-in tariff or export control.

Work modes:  

Self-use 

Priority: load>battery>grid

This mode applies the area that has low feed-in 
tariff and high electricity price.

Work modes:  

Force time use

Priority:battery>load>grid

(when charging)

Priority:load>battery>grid

(when discharg-

ing)
This mode applies to the area that has peak 
and valley electricity price. User can use off-
peak electricity to charge the battery. 

·

In the case of the external generator, the 

power generated will be used to supply the 
local loads first, then to charge the battery. 
The redundant power will export to the 
public grid as set in Export Control.

·

The charging and discharging time can be 

set flexibly. 

·

In the case of the external generator, the 

power generated  will be used to supply the 
local loads firstly, then export to the public 
grid. The redundant power will charge the 
battery.
·In the absence of the external generator, or 

     

EPS Status

When the grid is off, system will supply 
emergency power from the battery to supply 
the EPS home loads. (Battery is necessary in EPS 
mode.)

Work modes:  

Back up mode

Priority:battery>load>grid

This mode applies to the area that has frequent 
power outages. And  this mode ensures the 
battery will has enough energy to supply when 
the grid is off.

the power is not enough, battery will discharge 
for local loads first, and grid will supply power 
when power generated is not enough or 
battery capacity reaches too low.

·

In the case of external power generation 

equipment, the power generated  will be used 
to charge the battery fully firstly, then supply 
the local loads. The redundant power will be 
exported to the public grid.

·

In the absence of an external power 

generation device, charge the battery with the 
public grid.

·

The inverter will switch to EPS mode only 

when the grid is abnormal.

Содержание X3-Fit-10.0-C

Страница 1: ...this manual belongs to Solax Power Network Technology Zhe jiang Co Ltd Any corporation or individual should not plagiarize partitially or fully copy including software etc and no reproduction or distr...

Страница 2: ...General Data 4 4 EPS output apply to version E only 4 3 Efficiency Safety and Protection apply to version E C 4 2 Internal Charger apply to version E C 4 1 AC output input apply to version E C 5 3 Mo...

Страница 3: ...Note provides tips that are valuable for the optimal operation of our product Warning Warning indicates a hazardous situation which if not avoided could result in death or serious injury 03 8 Setting...

Страница 4: ...rrosive substance Authorized service personnel must use insulated tools when installing or working with this equipment The unit contains capacitors that remain charged to a potentially lethal voltage...

Страница 5: ...l be conducted by licensed electrician and shall comply with Australia National Wiring Rules Battery Safety Instructions SolaX X3 Retro Fit series inverter can only work with high voltage battery for...

Страница 6: ...operating and servicing the unit If ignored physical injury or death may follow or damage may occur to the unit Read this instruction before you work on the unit If you are unable to understand the d...

Страница 7: ...he inverter will stop with an overload fault warning Please confirm with the local grid supplied whether there is any special regulation for connecting to the grid Digram A applies to the wiring rules...

Страница 8: ...redundant power will export to the public grid as set in Export Control The charging and discharging time can be set flexibly In the case of the external generator the power generated will be used to...

Страница 9: ...10 0E X3 Fit 10 0C 8000 8000 11 6 12 8 10000 10000 14 5 16 0 10000 10000 14 5 16 0 400V 230VAC 380V 220VAC 50 60 8000 11 6 12 8 8000 11 6 12 8 10000 14 5 16 0 10000 14 5 16 0 400V 230VAC 380V 220VAC 4...

Страница 10: ...l Transformerless RS485 Meter WiFi optional DRM USB ISO alarm Backlight 20 4 character 10 years optional Standard 5 years Max Battery charge discharge efficiency 96 00 96 50 4 4 EPS output apply to ve...

Страница 11: ...ent temperature in the range of 20 to 60 The slope of the wall should be within 5 The wall for mounting the inverter should meet conditions below 1 Solid brick concrete or strength equivalent mounting...

Страница 12: ...rter 1 3 Hammer the expansion tubes in the holes and tighten them Then install the wall bracket with the expansion screws The screwdriver Torque 4 5 0 2Nm Installation tools crimping pliers for bindin...

Страница 13: ...a 3 3 Remove 12mm of insulation from the end of wire 3 4 Insert stripped wires into AC terminal and insure all conductor strands are captured in the AC terminal 3 5 Crimp the AC terminal head by using...

Страница 14: ...de above espescially for the wiring of neutral line grounding and RCD please contact us before any operation Electrical Connection Electrical Connection 24 25 EPS wiring diagram The below diagram are...

Страница 15: ...ut power When an over load occurs please adjust the EPS loads to make sure it is within the EPS output power range then turn the inverter back on For the nonlinear load please make sure the inrush pow...

Страница 16: ...se ensure that all the inverters software version must be the same otherwise the parallel function will not work Step1 Connect all inverters communication together by connecting network cables between...

Страница 17: ...l of all slaver inverters energy management and distribution control Once the master inverter comes with an error and stop working all the slavers will stop simultaneously But the master can work inde...

Страница 18: ...erter and battery is CAN with a RJ45 connector BMS PIN Definition Note The battery communication can only work when the battery BMS is compatible with the inverter Step4 Tighten the screw connectors T...

Страница 19: ...ath and insert the commu nication cable through the cable nut Electrical Connection Electrical Connection 36 37 Meter is used for monitoring the power usage for entire house at the meantime inverter w...

Страница 20: ...t the communication terminal into the BMS port Step1 Disassemble the BMS cable gland Step2 Prepare a communication cable without sheath and insert the commu nication cable through the cable nut Step1...

Страница 21: ...IN definition and port position will be slightly different COM Port COM DRM is provided to support several demand response modes by emitting control signals as below DRM1 5 DRM2 6 DRM3 7 DRM4 8 3 3V D...

Страница 22: ...er manual Pocket GPRS user manual for more details 6 9 LAN Connection LAN communication is the standard communication interface It can transmit the data between the router and inverter via the local n...

Страница 23: ...are commissioned in Italy The Italian standard requires that all inverters feeding into the utility grid are equipped with a self test function in accordance with CEI 0 21 During the self test the in...

Страница 24: ...SP respectively It will be like Update ARM 618 00098 00_Hybrid_X3G3_Manager_VX XX_XX XX usb Update DSP 618 00096 00_Hybrid_G3X3_Master_VX XX_XX XX hex VX XX is version number xx xx is le compilation d...

Страница 25: ...s Off The inverter is in fault status Constant green The battery communication is working Flashing green The battery communication is normal and in idle status Off The battery does not communicate wit...

Страница 26: ...lease refer to the inverter for the most updated structure Inverter DSP2 Self Test Charger setting Inv Warning Reset Inv Energy Factory Reset 49 Hot Standby Settings Power Limit BAT M SN BAT PS1 SN BA...

Страница 27: ...is plugged with a smart plug this status shows the real time load power include load1 power and load 2 power L1 Power 0W Load b Charger This status shows the charger situation of the system including...

Страница 28: ...EPS Yield b EPS Yield The EPS Yield function contains charger yield for today and total Inverter Yield EPS Yield Load Consume History Inv Warning Load 1 consume Load 2 consume Load consume c Load cons...

Страница 29: ...ssword to operate most of the professional settings The installer password is 2014 Date Time Language Ethernet Setting b Language This inverter provides several languages for customer to select a Date...

Страница 30: ...Mode Charge Start time 2 08 00 Work Mode Charge End time 2 08 00 Work Mode Setting Setting 56 57 e Relay Control Relay Control is a reserved function which can control designated load intelligently b...

Страница 31: ...notice Item 7 1 2 3 4 5 6 Country VDE 0126 ARN 4105 German AS 4777 Australia G98 2 UK EN 50438_NL Netherland CEI 0 21 Italy IEC61727_In India Standard German g 1 2 Power Factor For specific country if...

Страница 32: ...EN50438_NL only OFPL_StartPoint FreqDropRate Frequency droop rate Under Frequency power limit start point Over Frequency power limit start point UFPL_StartPoint OFPL_StartPoint Apply to EN50438_DK on...

Страница 33: ...according to different loads connected with each phase meter load1 2KW load2 3KW load3 4KW three phase inverter 3kw 3kw 3kw If 9kw AC power can be exported each phase power will be divided equally as...

Страница 34: ...Charger Current 35A Battery Awaken Charger NO For Lithium battery For Lead acid Battery Charge Absorp Voltage Charger Charge Float Voltage 0 0V Charger 0 0V Discharge cut Voltage 0 0V Charger Charge M...

Страница 35: ...EPS output is overloaded Frequency can be set to 50 or 60Hz based on your load loads EPS auto restart is used for restarting EPS output power manually or automatically Choose disable means the EPS out...

Страница 36: ...eter Setting X3 Retro Fit inverter with Energy meter connected can achieve hybrid functions You can disable the meter function then it can work as a normal grid tied inverter without PV and meter conn...

Страница 37: ...and pocket GPRS Register2 SN it indicates the serial number of built in Ethernet About This interface shows basic information of the inverter including inverter serial number Register1 serial number R...

Страница 38: ...seek help from installer 72 73 Troubleshooting AC10M Volt Fault The grid voltage is out of range for the last 10 Minutes The system will back to normal if the grid is back Or seek help from installer...

Страница 39: ...can not go back to normal state 74 75 Troubleshooting BMS_External_Err Battery Fault external fault Please contact battery suppiler BMS_Internal_Err Battery Fault internal fault Please contact battery...

Страница 40: ...ease contact the installer or SolaX to arrange qualified person who has adequate training knowledge and practical experience to perform these tests Please kindly noted this action is not covered by wa...

Отзывы: