IMP Commands 3595 4C User Manual Part Two
1-50
35952350 (CH01/AA)
Notes:
1.
If
n
= 20, Watchdogs are disabled.
2.
Alarm checking operates only for scanned channels, NOT for single measurements.
3.
The
CH GO
command stays in operation, unless:
a.
it is overridden by a
CH MO
command, or
b.
another
CH GO
command is received, or
c.
the Watchdog is enabled (channel 20 only). This command sets the MOde database to MO
80x
,
where
x
= the ‘Go’ state for the channel.
4.
The state of the digital output may be read at any time by measuring or scanning the channel.
5.
The group may consist of one alarm element only. If
p
= 2, no alarms need be specified – alarm
checking is disabled for all alarms previously specified.
6.
On alarm, the defined digital output is active. ‘Active’ can be defined as ‘switch closed’ or ‘switch
open’, depending on the value of
p
in the command string. This gives the option of an active alarm
when the IMP is non-functional.
Consider a requirement to disable a machine when off-limit readings are obtained for oil temperature,
oil pressure, or both, or monitoring equipment is non-functional. The oil temperature should be in the
range –10 to +95
°
C. The oil pressure should be in the range 1 to 3bar. The channel definitions for
this scenario could be:
a. Minimum acceptable oil temperature on channel 1 (low limit): CH1LL-10.
b. Maximum acceptable oil temperature on channel 1 (high limit): CH1HL95.
c. Minimum acceptable oil pressure on channel 2 (low limit): CH2LL1.
d. Maximum acceptable oil pressure on channel 2 (high limit): CH2HL3.
e. Define channel 19 associated with the above alarm group: CH19GO001L01H02L02H.
(Note that alarms use data post-unit conversion or post-linearisation.)
While the IMP is powered-down, the digital output is open, thus disabling the machine. When the IMP
first powers-up, the machine remains disabled. When CH19GO command is sent, the output is
switched into the alarm state (i.e. no change in this case) thus disabling the machine. Once the IMP
has read the machine parameters and determined that none are in alarm, it closes the output switch
and, thus, enables the machine.
Содержание 3595 4C
Страница 1: ...Precision measurement solutions 3595 4C PC to S Net Interface USER MANUAL 35952350...
Страница 2: ...ii 35952350 2001 SOLARTRON MOBREY LIMITED...
Страница 6: ...vi 35952350...
Страница 7: ......
Страница 8: ......
Страница 10: ...1 ii 35952350...
Страница 12: ...1 iv 35952350...
Страница 48: ...Programming the 3595 4C Interface card 3595 4C User Manual Part One 3 20 35952350 CH03 AA...
Страница 49: ...3595 4C PC to S Net Interface User Manual PART TWO IMP Commands and Responses...
Страница 50: ...2 ii 35952350...
Страница 52: ...2 iv 35952350...
Страница 108: ...IMP Commands 3595 4C User Manual Part Two 1 56 35952350 CH01 AA...
Страница 110: ...Results and Error Formats 3595 4C User Manual Part Two 2 2 35952350 CH02 AA...
Страница 122: ...Database Structure 3595 1H and 1J IMP 3595 4C User Manual Part Two A 2 35952350 APPX A AA...
Страница 126: ...Database Structure 3595 1H and 1J IMP 3595 4C User Manual Part Two A 6 35952350 APPX A AA...
Страница 127: ......