Figure 29: Example of Ethernet connection
To connect the Ethernet cable:
1. Remove the inverter cover as described in
Removing the Inverter Cover on page 69.
2. Open the communication gland #1.
CAUTION!
The gland includes a rubber waterproof fitting, which should be used to
ensure proper sealing.
ATTENTION!
Le cote interne du gland contient une rondelle qui doit être utilisée pour
une bonne étancheïté.
3. Remove the plastic seal from one of the large opening .
4. Remove the rubber fitting from the gland and insert the CAT5/6 cable through the
gland and through the gland opening in the inverter .
5. Push the cable into the cut opening of the rubber fitting.
Figure 30: Rubber fitting
CAT5/6 standard cables have eight wires (four twisted pairs), as shown in the diagram
below. Wire colors may differ from one cable to another. You can use either wiring
standard, as long as both sides of the cable have the same pin-out and color-coding.
-
Three
Phase
System
Installation
Guide
MAN-01-00527-1.
2
70
Creating an Ethernet (LAN) Connection