To connect the AC grid to the Safety Switch – 9kW, 10kW, 20kW:
1. Strip 05
⁄
16'' (8mm) of the AC wire insulation.
2. Insert the AC conduit into the AC-side drill guide that was opened.
NOTE
Connect the equipment grounding before connecting the AC wires to the
AC.
Veillez à relier le conducteur de PE (la terre) avant de connecter les fils CA
au bornier CA.
3. Connect the wires as follows:
1. Use a standard flat-blade screwdriver to connect the wires to the spring-clamp
terminals (See
2. The screwdriver blade should fit freely in the terminal opening. Too large a blade
can crack the plastic housing.
3. Insert the screwdriver, press the release mechanism and open the clamp.
4. Insert the wire into the round opening and remove the screwdriver – the wire is
automatically clamped.
Figure 24: AC Spring-clamp terminal – 9kW, 10kW, 20kW inverter