Default Trip Limits and Times According to IEEE1547
NOTE
The inverters are equipped with adjustable utility protective function set-points, and can be aggregated above 30kW on a
single Point of Common Connection. The default settings are in compliance with IEEE1547. Utility authorization is required
to change these set-points.
Voltage Range (% of Base Voltage) Maximum Clearing Time (Sec)
V < 50%
0.16
50 % < V < 88%
2.00
110% < V < 120%
1.00
V > 120 %
0.16
Frequency Range (Hz)
Maximum Clearing Time (Sec)
> 60.5
0.16
< 59.3 (Hawaii – 57)
0.16
Safety Switch
Specifications
Unit
Maximum DC voltage
500
Vdc
Maximum DC current
32
Adc
Nominal AC voltage
208/480
Vac
Maximum AC current
32
Aac
Ambient temperature
-40 to 140 / -40 to +60
°F /°C
Weight
6.6 / 3.0
lb/kg
MAN-01-00527-1.
2
Technical
Specifications
-
Three
Phase
Inverters
(North
America)
Technical Specifications - Three Phase Inverters (North America)
99