Connecting the Inverter
Inverter Connection Overview
The SolarEdge inverter can be configured in the field for an AC grid,
including AC voltage and frequency. If the inverter’s default settings are
not suited to the country of the installation site, then please refer to page 71
for a description of how to configure the inverter for the required country.
With the SolarEdge Configuration Tool, you can configure the inverter’s
AC settings to different settings than those provided by default for the
country of the installation site, or perform other modifications. A full
description of the Configuration Tool is provided in the
SolarEdge
Configuration Tool Software Guide
.
Refer to the following table to determine the correct fuse size to use at the
connection point of the Single Phase Inverter to the grid:
Inverter
Maximum Output Current
Suggested Fuse
SE7k
11.5 A
12 A
SE8k
13.5 A
16 A
SE9k
15.5 A
16 A
SE10k
17.5 A
20 A
SE12k
19.5 A
25 A
WARNING!
For more wiring information, you may refer to the Application Note called
SolarEdge
Recommended AC Wiring,
which can be accessed from the SolarEdge website.
WARNING!
You should also refer to the technical specifications in
Appendix B, Technical
Specifications
on page 81. Pay special attention to the inverter specifications
because they may differ slightly in different countries.
WARNING!
It is essential to connect the PE (ground) wiring before connecting the AC Line and
Neutral wires.