88
UPS for 208 Vac Grid, B120US Installation Guide, doc. rel. 3.0
21.
On the system controller LCD screen select
Operations > transfer load to inverter
.
22.
Verify that the load is being supported by the inverters on the Status screen.
Table 14: Position of the CBs in normal mode
Battery box input
(on battery box)
Rectifier ac input
(CB 2)
Bypass ac input
(CB 3)
UPS AC output
(CB 5)
Maintenance bypass
(CB 6)
ON
ON
ON
ON
OFF