Specifications (Sechnische Daten)
34
13.0 S
PECIFICATIONS
(S
ECHNISCHE
D
ATEN
)
Table 7
UPS specifications
Model Number
S4K5U6000-5
S4K5U4500-5
Model Rating
6KVA / 4,200W
4.5KVA / 3,150W
Dimensions mm (in.)
Unit, W x D x H
221 x 547 x 430 (8.7 x 21.5 x 16.9)
Shipping, W x D x H
560 x 690 x 500 (22.05 x 27.17 x 19.7)
Weight kg (lbs)
Unit
67 (151)
67 (151)
Shipping
79.5 (175.3)
79.5 (175.3)
Input AC Parameters
Nominal Operating Frequency
50 or 60Hz (Factory Default = 50)
Factory Default VAC
230VAC
User Configurable VAC
220/230/240VAC
(May be modified using configuration program)
Operating Voltage Range Without
Battery Operation
176 – 276VAC
Maximum Allowable VAC
276VAC
Input Frequency Without Battery
Operation
40 - 70Hz
Input Power Connection
(See
3.3 - Removable Power Distribution Box
)
Output AC Parameters
Factory Default VAC
230VAC
Output Connections
(See
3.3 - Removable Power Distribution Box
)
Frequency
50Hz or 60Hz, Nominal
Waveform
Sinewave
Main Mode
Overload
>200% for 96 milliseconds; 131 - 199% for 2 seconds;
112- 129% for 10 seconds with transfer to bypass
Battery Parameters
Type
Valve-regulated, non-spillable, lead acid
Quantity x V
20 x 12V
Battery Mfr. / Part #
Yuasa / REW 28-12
Back-up Time
See
Table 6 - Battery run times
Recharge Time (Internal Batteries)
3 hrs. to 90% capacity after full discharge into 100% load
Bypass Protection Limits
Disable Bypass operation
If input voltage exceeds ±15% of the nominal voltage
Re-enable Bypass operation
If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation
When the input frequency prevents synchronous operation
Environmental
Operating Temperature
0
°
C to +40
°
C (+32
°
F to +104
°
F)
Storage Temperature
-15
°
C to +50
°
C (+5
°
F to +122
°
F)
Relative Humidity
0-95% non-condensing
Operating Elevation
Up to 2000m (6600 ft) at 40
°
C (104
°
F) without derating
15,000m (50,000 ft.) maximum
Storage Elevation
Audible Noise
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
Agency
Safety
EN62040-1-1; TUV/GS
EMI/EMC/C-Tick EMC
EN50091-2 and AS 62040-2: 2002, Class A; CE EMC Directive
ESD
EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility
EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient
EN61000-4-4, Level 4, Criteria A
Surge Immunity
EN61000-4-5, Level 3, Criteria A
Transportation
ISTA Procedure 1B