Configuration Program
18
7.0
C
ONFIGURATION
P
ROGRAM
The final step of installation may require custom configuration of your UPS using the enclosed config-
uration program. Some configuration settings may be changed only while the UPS is off. These should
be set before the UPS is put into full-time service powering the critical load.
For most users operating with 230VAC and with no external batteries, the factory default settings
will be adequate.
7.1
S4K5U6000-5 and S4K5U4500-5 Configuration Program Features
• Select one of three L-N output voltages to match local voltages.
• Enable/Disable Auto-Restart.
• Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.
• Set the Low Battery Warning alarm time from 2 to 30 minutes.
• Enable/Disable the Auto-Battery test.
• Set the Auto-Battery test to 7, 14, 21, or 28 days.
• Specify the number of external battery cabinets connected to the UPS to adjust the remaining run
time calculations reported by Sola/Hevi-Duty software products.
• Modify the shutdown setting of DB-9 pin 6 (for information on pin assignments, see
Table 2
).
7.1.1
What You Will Need
In addition to the S4K5U UPS, you will need the configuration program diskette and serial cable
(beige or tan, 3-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) included in the UPS accessory box.
A Windows 95® or later computer, desktop or laptop, is also required to set up and run the configura-
tion program.