Maintenance
27
1. Remove the 5U bezel panel on the front of the UPS
by removing the screws located on the sides of the
bezel (see illustration at right).
2. Remove battery access door by loosening the
captive screws and tipping the panel forward. Lift
to remove it from the main cabinet.
3. Use a Phillips (cross-head) screwdriver to remove
the screw in the battery retaining bracket on each
battery pack (see illustration at right). Remove the
retaining brackets.
4. Disconnect the battery connectors in the front of
each battery pack.
5. Lift the internal connector out of the way and slide
the battery out of the UPS. Support the weight of
the battery to prevent it from falling.
6. Unpack the new battery assembly, taking care not
to destroy the packing. Compare new and old
battery assemblies to make sure they are the
same. If so, proceed with
Step 7
; otherwise STOP
and contact your local dealer, Sola/Hevi-Duty
representative or the Sola/Hevi-Duty Technical
Support Services.
7. Line up and slide in the new replacement battery
pack while holding the internal connector out of
the way.
8. Reconnect the electrical connections for each
battery pack.
9. Install the battery retaining brackets using the
Phillips removed earlier.
10. Install the battery access panel and tighten the
captive screws.
NOTE
These are hot-swappable replacement
batteries. However, caution should be
exercised because during this procedure the
load is unprotected from disturbances and
power outages.
!
UPStation GXT
AC INPUT
- +
BATTERY UPS ON
BYPASS
Retaining bracket
Retaining screw
!
UPStation GXT
AC INPUT
- +
BATTERY UPS ON
BYPASS
Battery Connectors
Battery Access Bezel Screws
5U Bezel with Battery Access
Door Behind Bezel