S4KC SEriES USEr MAnUAL |
43
Table 7: UPS Specifications
Parameters
Model Number: S4K5U6K5C
AgENCy
Safety
iEC62040-1:2008 Version
EMI/EMC
iEC/En/AS 62040-2 2
nd
Edition (Cat 2—Table 6)
ESD
En61000-4-2, Level 4, Criteria A
Radiated Susceptibility
En61000-4-3, Level 3, Criteria A
Electrical Fast Transient
En61000-4-4, Level 4, Criteria A
Surge Immunity
En61000-4-5, Level 3, Criteria A
Transportation
iSTA Procedure 1A
Table 8: Operating Temperature Parameters
Ambient Temperature
Model Number: S4K5U6K5C
pf @ 30°C ±3°C [pf @ 86°F ±5.4°F]
0.8 pf
pf @ 40°C ±3°C [pf @ 104°F ±5.4°F]
0.8 pf
Table 9: Power Distribution Specifications
Parameters
Model Number: S4KPAD2-CEHwMBSC
Used with UPS Model
S4K5U6K5C
Power Distribution Box Includes:
Two (2) iEC320 C19 16 A/250 V Sockets
Eight (8) C13 10 A/250 V Sockets
Manual bypass switch with indicator lamp
Ampere Rating
32 A
Input/Output Power Connections
3-wire hard wired, 6–10 mm
2
(8–10 AWG)
User-Supplied Input Branch Circuit Breaker
32 A