26
| 7.0 Controls & indicators
7.0 Controls & indicators
On/Alarm Silence/Manual
Battery Test button
Standby/Manual Bypass button
Fault indicator
Load Level indicators
Battery Level indicators
Ac Input indicator
Inverter indicator
Battery indicator
Bypass indicator
Figure 19: Operation and display panel
7.1 On/Alarm Silence/Manual Battery Test Button
This button controls output power to connected load(s) and has three functions:
•
On:
Pressing this button for four seconds will start the UPS.
•
Alarm Silence:
To silence alarms, press this button for at least one second. After the alarm is silenced, the UPS will
reactivate the alarm system to alert of additional problems.
NOTE:
The Low Battery and Bypass reminder alarms CAnnOT be silenced.
•
Manual Battery Test:
To initiate a manual battery test, press the On button for at least one second while operating
from mains power with no alarm conditions present. if only three of the five Battery LEDs illuminate, allow the UPS
to recharge the batteries for 24 hours. After 24 hours, retest the batteries.
After the batteries have been retested, if only three of the five Battery LEDs illuminate, contact your local dealer,
SolaHD representative, or SolaHD Technical Support.
7.2 Standby/Manual Bypass Button
This button controls output power to connected load(s) and has dual functions: Standby and Manual Bypass.
NOTE:
Pressing the Standby/Manual Bypass button once will transfer the load to bypass power and the load will be
unprotected from disturbances in the mains supply. Pressing the Standby/Manual Bypass button twice within four
seconds while on bypass will cut off power to the output sockets and connected loads. Perform all necessary shutdown
procedures on connected loads before pressing this button twice.