HYD 3K~6K-EP
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
。
- 28 -
RS485 wires are connected in parallel between inverters, (NOTE
:
When
multiple inverters are connected via RS485 wires, set communication address to
differentiate the inverters
,
please refer to this manual<6.3.1System
setting
→
8.Communication Addr>)
Fig.4-11 RS485 connection(cascade of monitoring between inverters)
2. Logic interface
The logic interface pin definitions and circuit connections are as follows:
Logic interface pin are defined according to different standard requirements
(
a
)
Logic interface for AS/NZS 4777.2:2015, also known as inverter demand
response modes (DRMs).
The inverter will detect and initiate a response to all supported demand
response commands within 2 s. The inverter will continue to respond while the
mode remains asserted.
Table 4-6 Function description of the DRMs terminal
Pin NO.
Function
8
DRM1/5
9
DRM2/6
10
DRM3/7
11
DRM4/8
12
DRM0
7
GND-S
(
b
)
Logic interface for VDE-AR-N 4105:2018-11, is in order to control
and/or limit the inverter’s output power.
The inverter can be connected to a RRCR (Radio Ripple Control Receiver) in
order to dynamically limit the output power of all the inverters in the installation.
Fig.4-12 Inverter – RRCR Connection
Содержание HYD 3000-EP
Страница 1: ...Shenzhen SOFARSOLAR Co Ltd Energy storage integrated inverter Product Model HYD 3K 6K EP User manual ...
Страница 13: ...HYD 3K 6K EP User manual Copyright Shenzhen SOFARSOLAR Co Ltd 8 ...
Страница 21: ...HYD 3K 6K EP User manual Copyright Shenzhen SOFARSOLAR Co Ltd 16 ...
Страница 36: ...HYD 3K 6K EP User manual Copyright Shenzhen SOFARSOLAR Co Ltd 31 Fig 4 15 Electrical connections Plan A CT ...