52
Model
SUNSYS-B10
Phase shift (cos
ψ
) at nominal
output power
(adjustable)
>0.99
(±0.8 on demand)
Efficiency
Max. conversion efficiency
≧
98.0%
European efficiency
≧
97.2%
General Data
Topology
Transformerless
Power consumption:
standby / night
≦
20W /
≦
1W
Protection degree
Outdoor / Chassis: IP65 / Fan: IP55
Heat dissipation
Force air cooling, variable fan speed according to temperature on heatsink
Acoustic noise level
≦
55dB(A)
Operating temperature range
- 20 ~ + 60
℃
Continuous Output power
temperature range
- 20 ~ + 45
℃
Max O/P power
(60
0
C, nominal voltage, linear
de-rating)
10000W
Max. Operating Temp. without
derating for nominal voltage
45
0
C
Humidity
100%, condensing
Altitude
Up to 2000m without power derating
Hazard substance restriction
Lead free, complied with RoHS GP2
Ground fault protection
Internal RCMU and Isolation detection function
DC disconnect (Optional)
EN/IEC standard approved DC Switch
Communication (Optional)
Standard: USB B type,
Front Bezel
Data logger
- Display: 128
×
64 pixels
- Function key × 5
- Standard: embedded
- Optional: removable
Normative references