26
5.
Three Operating States:
Standby
:
During normal operation, the PV inverter is in
“Standby” state when the open circuit voltage is between
200V to 250V.
Pac:0W
Vdc:220/210V
Vac:219.4/219.3/219.3V
Temperature:26.8°C
Status:Standby
21.04.12 15:01
Waiting :
Between 251V and 349V at DC side, the Inverter is in
“Waiting” state. In the meantime, the Inverter
keeps checking both DC and AC conditions and waiting for connection.
Pac:0W
Vdc:260/329V
Vac:219.4/219.3/219.3V
Temperature:26.8°C
Status:Waiting
21.04.12 15:01
Normal:
To be in
“Normal” state, voltage on DC side must be 350V or above. To check the DC wire connection,
this Inverter tries to disturb its input power for every starting-up. During the process, user can see the
DC power reading drift.
Pac:2300W
Vdc:450/420V
Vac:219.4/219.3/219.3V
Temperature:26.8°C
Status:Normal
21.04.12 15:01
Green backlight
Green backlight
Green backlight
Содержание SUNSYS - B10
Страница 1: ...SUNSYS B10 Installation and Operation Manual ...
Страница 15: ...15 D Check and ensure the device is properly fixed to the bracket in the proper direction ...
Страница 36: ...36 ...
Страница 37: ...37 ...
Страница 38: ...38 ...
Страница 39: ...39 ...
Страница 40: ...40 ...
Страница 41: ...41 ...
Страница 42: ...42 ...
Страница 54: ...54 ...