33
Select the desired value by pressing “
↓
” o “
↑
” and confirm each value pressing “OK”.
The item in the “Power Factor Curve” setting page are refer at the following picture.
5.
Curve Q(U): by pressing “OK” is possible to set the parameters of curve of management of the reactive
power in function of grid voltage.
Select the desired value by pressing “
↓
” o “
↑
” and confirm each value pressing “OK”.
The item in the “Power Factor Curve” setting page are refer at the following picture.
Power Factor Curve
With Power Percent
V lock-in: 241.4V
V lock-out:230.0V
Node 1: 20% +1.00pf
Node 2: 40% +1.00pf
Node 3: 50% +1.00pf
Node 1: 100% -0.90pf
Q Curve VS Voltage %
Type: A
P lock-in: 20%Pn
P lock-out: 5%Pn
Node 1: 90% +48.4%Q/S
Node 2: 92% + 0.0%Q/S
Node 3: 108% + 0.0%Q/S
Node 1: 110% -48.4%Q/S