Product safety
• The UPS connection instructions and operation described in the manual must
be followed in the indicated order.
• UPS enclosure IP rating IP20.
•
CAUTION - To reduce the risk of fire, the unit connects only to a circuit provided
with branch circuit overcurrent protection.
• The upstream circuit breaker for Normal AC/Bypass AC must be easily
accessible. The unit can be disconnected from the AC power source by
opening this circuit breaker.
• An additional AC contactor is used for back feed protection and must comply
with IEC/EN 62040-1 (the creepage and clearance distances should meet the
basic insulation requirements for pollution degree 2).
• Disconnection and overcurrent protection devices should be provided by others
for permanently connected AC input (Normal AC/Bypass AC) and AC output
circuits.
• Check that the indications on the rating plate correspond to your AC powered
system and to the actual electrical consumption of all the equipment to be
connected to the system.
• Never install the system near liquids or in an excessively damp environment.
• Never allow a foreign body to penetrate the system.
• Never block the ventilation grates of the system.
• Never expose the system to direct sunlight or source of heat.
• If the system must be stored prior to installation, storage must be in a dry place.
• The admissible storage temperature range is -25°C to +55°C without battery
(-15°C to +40°C with battery).
• TN-S/IT/TN-C/TT of electrical supply system may be connected by UPS.
• This UPS may be provided with a maximum of 6 extension battery cabinets or
equivalent.