ITYS 6-10 kVA - 551431A - SOCOMEC
23
EN
The following table shows the Buttons status and description:
BUTTONS
FUNCTION
DESCRIPTION
ESC
Power on
The Unit can be turned on by pressing the button for more than
100 milliseconds and less than 1 second, without utility input and
battery connected
Turn on
Press the button more than 1 second to turn on the UPS
Turn off
Press the button more than 3 seoconds to turn off the UPS
ESC
Scroll up
Press to scroll up the menu option
ESC
Scroll down
Press to scroll down the menu option
ESC
Enter menu
Select/Confirm the current selection
ESC
Exit the present menu Press to exit present menu to main menu or the higher-level
menu without changing the setting
Mute buzzer
Press the button to mute the buzzer temporarily; once a new
warning or fault is active, the buzzer will be activated again
NO.
STATUS
ALARM
1
Battery mode
Beep once every 4 sec
2
Battery mode with battery low
Beep once every sec
3
Bypass mode
Beep once every 2min
4
Overload
Beep twice every sec
5
Warning active
Beep once every sec
6
Fault active
Beep continuously
7
Button function active
Beep once
The buzzer will be temporality silenced if one or more alarms are active and silence
button is pressed. The buzzer will beep again if any new alarm becomes active.
Backlight
The LCD backlight automatically dims after 10 minutes of inactivity.
Press any button to restore the screen.