ITYS 6-10 kVA - 551431A - SOCOMEC
45
EN
MODELS
ITY3-
TW060B
ITY3-
TW060LB
ITY3-
TW108B
ITY3-
TW100B
ITY3-
TW100LB
ITY3-
TW110B
Charging
current
(1)
Range
1~4A
2~12A
1~4A
1~4A
2~12A
1~4A
Default
1.4A
4A
2A
2A
4A
2A
Output
Rated voltage
(Phase voltage)
220/230/240VAC
Overload on normal
mode
105%-125% Load, 10 minutes transfer to Bypass;
125%-150% Load, 30 seconds transfer to Bypass;
>150% Load, 0.5 seconds transfer to Bypass
Short-circuit current on
normal mode
54A for
200ms max
54A for
200ms max
113A for
200ms max
113A for
200ms max
113A for
200ms max
113A for
200ms max
Transfer Time Line<->Battery
0ms
Transfer Time INV<->Bypass
0ms
BATTERY
Rated voltage
192VDC
Battery number
16 PCS
ENVIRONMENT
Ambient temperature
0°C ~ 50°C (Derating 50% above 40°C)
Relative humidity
0 ~ 95%(no condensing)
Operating altitude
<3000m (Derating use above1km, the load should de-rating 1% every
up 100m)
Storage temperature
(with battery)
-15°C ~ 40°C
Storage temperature
(without battery)
-25°C ~ 55°C
CRITERION
Safety
IEC EN 62040-1, AS 62040-1
EMC
IEC EN 62040-2 , AS 62040-2
Performance
IEC EN 62040-3
Manufacture
ISO 9001:2015, ISO 14001:2015
(1) In free running mode and converter mode, UPS needs to be de-rated to 60% capacity (rated output power
and maximum charging current).
(2) @ 220VAC input phase voltage, rated output power and maximum charging.
Note:
this is a category C3 UPS product. In a residential environment,
this product may cause radio interference, in which case the user may be
required to take additional measures.